Siemens SENTRON 3VL System Manual page 147

Switching/protection devices, molded-case circuit breakers
Hide thumbs Also See for SENTRON 3VL:
Table of Contents

Advertisement

Table 12- 3
IEC 60947-2
For rated currents above 25 A. The VL160X is not available with a rated voltage of 690 V AC for
3)
rated currents of 16 A and 20 A.
At 240 V AC, 415 V AC, and 525 V AC max. 5% overvoltage; at 440 V AC, 500 V AC and 690 V
4)
AC max. 10% overvoltage.
At 250 V DC, 500 V DC and 600 V DC max. 5% overvoltage.
5)
The voltage values apply for at least 3 conductor paths in series, see also "Suggested circuits for DC
networks" in the Chapter "Application planning".
Table 12- 4
IEC 60947-2
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
Standard switching capacity VL160X, VL160 to VL400
SENTRON VL - N rated breaking current (kA) balanced (standard switching capacity)
Type
SENTRON
Up to 240 V AC
4)
Up to 250 V DC
5)
Standard switching capacity VL630 to VL1600
SENTRON VL - N rated breaking current (kA) balanced (standard switching capacity)
Type
SENTRON
Up to 240 V AC
4)
Up to 250 V DC
5)
Vl160X
I
/I
cu
cs
65/65
415 V AC
40/40
440 V AC
25/20
500 V AC
18/14
690 V AC
8/4
3)
30/30
500 V DC
--
600 V DC
--
VL630
I
/I
cu
cs
65/65
415 V AC
45/45
440 V AC
35/26
25/20
525 V AC
690 V AC
20/10
32/32
500 V DC
--
600 V DC
--
Technical data
12.1 Technical overview
VL160
VL250
I
/I
I
/I
cu
cs
cu
cs
65/65
65/65
40/40
40/40
25/20
25/20
25/20
25/20
12/6
12/6
32/32
32/32
--
--
--
--
VL800
VL1250
I
/I
I
/I
cu
cs
cu
cs
65/65
65/35
50/50
50/25
35/26
35/26
25/20
25/20
20/10
20/10
--
--
--
--
--
--
VL400
I
/I
cu
cs
65/65
45/45
32/26
25/20
15/8
32/32
--
--
VL1600
I
/I
cu
cs
65/35
50/25
35/26
25/20
20/10
--
--
--
147