Siemens SENTRON 3VL System Manual page 52

Switching/protection devices, molded-case circuit breakers
Hide thumbs Also See for SENTRON 3VL:
Table of Contents

Advertisement

Functions
5.1 Current protection
Standard features
● Mechanical trip display:
The Reset button pops out when the RCD module trips the circuit breaker.
● Reset button:
This must be manually reset after the circuit breaker has been tripped by the RCD module.
The circuit breaker can only be reset and switched on again after the RCD module has been
reset.
● Cover:
Modifiable settings for ∆t and I
A sealable transparent cover is available for preventing modification.
● LED displays:
– 3 LEDs (green/yellow/red) indicate the level of the leakage/fault current. The blinking
– Green: I
– Green + yellow: 25% < I
– Green + yellow + red: I
● Test button:
The functionality of the RCD module is checked with the test button. If the test button is
pressed, differential current is simulated on a test winding attached to the summation current
converter. If it is functioning correctly, the RCD module must trip the circuit breaker.
The test button must remain pressed for at least the period of the set delay time Δt.
● A network disconnection device:
– makes it possible to disconnect the evaluation electronics of the RCD module from the
– Limitation of the maximum r.m.s. withstand voltage to an r.m.s. value of 3500 V AC for
● Protection function up to 50 V AC between phase and neutral conductor
● The RCD module has a surge withstand strength of I
wave is defined as 8 / 20-µs waveform.
● The RCD module does not trip in the case of making currents.
Δt ≥ 0 I
Δt ≥ 60ms I
● The circuit breaker combination with differential current protection can be supplied from
both sides.
● Suitable for circuit breaker standard accessories – covers, phase barriers, wire
connectors.
52
indicator signals that the SENTRON VL RCD module is ready for operation.
= 25% of the set value, the cable is live
circuit without removing the primary cable or the busbars (e.g. before insulation tests).
this feature.
= 3000 A
rms
= 20 x I
x √2
peak
n
.
∆n
< 50 of the set I
value
∆n
= 50% of the set I
value
∆n-
= 2000 A. The standard surge
peak
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01