Type
Stored-energy motorized operating mechanism (synchronization-enabled)
Power consumption [VA / W]
Rated control supply voltage V
[50 / 60 Hz V AC]
Rated control supply voltage V
[V DC]
DIAZED fuse
(performance class gG,
characteristic slow) [A]
Miniature circuit breaker
(C characteristic in accordance
with DIN VDE 0641) [A]
Operating range [V]
Minimum command duration
with V
[ms]
s
Max. command duration,
connection-dependent
1)
Total closing time [ms]
Break time [s]
Pause between the commands
OFF and ON [s]
Pause between the commands
ON and OFF [s]
Max. permissible switching
frequency [1/h]
x: Available
Changeover contact also permissible, but note the pause times between ON and OFF.
1)
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
VL160X
VL160
3VL1
3VL2
< 100
< 100
42-48 / 60
s
24 / 42-48 / 60
s
4
4
0.85 to
0.85 to
1.1 x V
1.1 x V
s
s
50
50
Jog/pushbutton or continuous command
< 100
< 100
< 5
< 5
> 5
> 5
> 1
> 1
120
120
VL250
VL400
VL630
3VL3
VL4
3VL5
< 100
< 200
< 250
110-127 / 220-250
110-127 / 220-250
2
2
0.85 to
0.85 to
0.85 to
1.1 x V
1.1 x V
1.1 x V
s
s
50
50
50
< 100
< 100
< 100
< 5
< 5
< 5
> 5
> 5
> 5
> 1
> 1
> 1
120
120
60
System overview
4.2 Key data
VL800
VL1250
VL6
3VL7
< 250
-
-
-
-
-
0.85 to
-
1.1 x V
s
s
50
-
-
< 100
-
< 5
-
> 5
-
> 1
-
60
-
VL1600
3VL8
-
-
-
-
-
-
-
-
-
-
-
-
-
39