Table 12- 7
IEC 60947-2
Table 12- 8
IEC 60947-2
At 240 V AC, 415 V AC, and 525 V AC max. 5% overvoltage; at 440 V AC, 500 V AC and 690 V
4)
AC max. 10% overvoltage.
At 250 V DC, 500 V DC and 600 V DC max. 5% overvoltage.
5)
The voltage values apply for at least 3 conductor paths in series, see also "Suggested circuits for DC
networks" in the Chapter "Application planning".
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
Very high switching capacity VL160X, VL160 to VL400
SENTRON VL - L rated breaking current (kA) balanced (very high switching capacity)
Type
SENTRON
Up to 240 V AC
4)
Up to 250 V DC
5)
Very high switching capacity VL630 to VL1600
SENTRON VL - L rated breaking current (kA) balanced (very high switching capacity)
Type
SENTRON
Up to 240 V AC
4)
Up to 250 V DC
5)
VL160X
I
/I
cu
cs
--
415 V AC
--
440 V AC
--
525 V AC
--
690 V AC
--
--
500 V DC
--
600 V DC
--
VL630
I
/I
cu
cs
200/150
415 V AC
100/75
440 V AC
75/50
525 V AC
50/38
690 V AC
35/17
32/32
500 V DC
32/32
600 V DC
32/32
Technical data
12.1 Technical overview
VL160
VL250
I
/I
I
/I
cu
cs
cu
cs
200/150
200/150
100/75
100/75
75/50
75/50
50/38
50/38
12/6
12/6
32/32
32/32
32/32
32/32
32/32
32/32
VL800
VL1250
I
/I
I
/I
cu
cs
cu
cs
200/150
200/100
100/75
100/50
75/50
75/50
50/38
50/38
35/17
35/17
--
--
--
--
--
--
VL400
I
/I
cu
cs
200/150
100/75
75/50
50/38
15/8
32/32
32/32
30/32
VL1600
I
/I
cu
cs
200/100
100/50
75/50
50/38
35/17
--
--
--
149