Siemens SENTRON 3VL System Manual page 176

Switching/protection devices, molded-case circuit breakers
Hide thumbs Also See for SENTRON 3VL:
Table of Contents

Advertisement

Technical data
12.10 Motor Protection
Circuit breakers for motor protection with adjustable trip class ETU 40M
Characteristic curve of circuit breakers for
motor protection with adjustable trip class
ETU40M
Table 12- 40 Circuit breakers for motor protection with adjustable trip class ETU40M
Circuit
breaker
VL160
VL250
VL400
VL630
176
Rated
Max. rated power of the
current I
motor at 50 Hz AC
n
[kW]
[A]
380 / 415 V
63
30
100
37, 45
160
55, 75
200
90, 110
250
132
315
160
315
200
500
250
These circuit breakers possess an
adjustable overload and short-circuit release
and an adjustable trip class. They are
current-limiting and have a phase failure
sensitivity feature. They are also equipped
with an LCD display for indicating the
current and for parameterization.
Communication via Profibus is possible.
Adjustable range
of the overload
protection I
R
500 V
[A]
37
25-63
55
40-100
75, 90
63-160
110, 132
80-200
160
100-250
200
126-315
250
126-315
355
200-500
System Manual, 03/2009, 110 0110 - 02 DS 01
Adjustable
Trip class TC
range of the
short-circuit
protection I
I
[s]
[A]
1.25-11 x I
5/10/15/20/30
n
1.25-11 x I
5/10/15/20/30
n
1.25-11 x I
5/10/15/20/30
n
1.25-11 x I
5/10/15/20/30
n
1.25-11 x I
5/10/15/20/30
n
1.25-11 x I
5/10/15/20/30
n
1.25-11 x I
5/10/15/20/30
n
1.25-12.5 x I
5/10/15/20/30
n
3VL molded-case circuit breakers

Advertisement

Table of Contents
loading

Table of Contents