Plug-in or withdrawable version:
Table 12- 24 Derating factors for thermomagnetic overcurrent trip unit + RCD module (plug-in or
Circuit
breaker
VL160X
VL160 &
VL160X
VL250
VL400
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
withdrawable version)
Trip unit
Thermomagnetic TM
From [A]
To [A]
16
40
50
100
125
160
200
250
200
250
315
400
Coefficient
at
40 °C
50 °C
1
1
1
0,97
1
0,88
1
0,85
1
0,97
1
0,85
Technical data
12.5 Derating factors
60 °C
70 °C
1
1
0,97
0,97
0,88
0,88
0,85
0,85
0,97
0,97
0,85
0,85