Siemens SENTRON 3VL System Manual page 179

Switching/protection devices, molded-case circuit breakers
Hide thumbs Also See for SENTRON 3VL:
Table of Contents

Advertisement

Table 12- 43 Undervoltage release for VL630 to VL1600
Operating voltage [V]
Drop (circuit breaker trips)
Pick-up (circuit breaker can be
switched on)
Power consumption
AC 50 / 60 Hz [VA]
DC [W]
Max. opening (release)
time [ms]
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
VL630
0.35-0.70 V
s
0.85-1.10 V
s
110-127 V
1.1
220-250 V
2.1
208 V
2.2
277 V
1.6
380-415 V
2.0
440-480 V
2.3
500-525 V
2.9
12 V
1.2
24 V
1.4
48 V
1.5
60 V
1.6
110-127 V
1.2
220-250 V
1.5
80
12.12 Undervoltage release
VL800
VL1250
0.35-0.70 V
0.35-0.70 V
s
0.85-1.10 V
0.85-1.10 V
s
1.1
1.1
2.1
2.1
2.2
2.2
1.6
1.6
2.0
2.0
2.3
2.3
2.9
2.9
1.2
1.2
1.4
1.4
1.5
1.5
1.6
1.6
1.2
1.2
1.5
1.5
80
80
Technical data
VL1600
0.35-0.70 V
s
s
0.85-1.10 V
s
s
1.1
2.1
2.2
1.6
2.0
2.3
2.9
1.2
1.4
1.5
1.6
1.2
1.5
80
179

Advertisement

Table of Contents
loading

Table of Contents