3.4.4 Function test of motor contactors K42 and K43

3.4.4 Function test of motor contactors K42 and K43
Performing the function test
1
2
3
138
Action
Start the robot system and turn the mode
switch to manual mode.
Press the three-position enabling device
to the middle position and then hold the
enabling device in this position.
Release the three-position enabling device.
© Copyright 2007-2018 ABB. All rights reserved.
Note
This test is passed if the event message
"10011 Motors ON state" appears in the
FlexPendant log.
If the event message "37001 Motor on ac-
tivation error" appears on the FlexPendant
log, the test is failed and the root cause of
the failure must be found.
This test is passed if the event message
"10012 safety guard stop state" appears
in the FlexPendant log.
If the event message "20227 Motor contact-
or conflict" appears in the FlexPendant
log, the test is failed and the root cause of
the failure must be found.
Product manual - IRC5 Panel Mounted Controller
3HAC047137-001 Revision: J