Options available on the valve

3.4.1. Autotrol Logix residential/commercial series auxiliary microswitch kits
The Logix residential/commercial series switch kits allow you to provide an electrical signal during
the valve operation. The switches can be wired independently in N.O or NC. The switches are available
for 0.1 Amp or 5 Amp rating.
3.4.1.1 Front mount
The microswitch is mounted behind the controller at the front end of the camshaft. The cam for this
switch is screwed to the front of the camshaft. This cam can be adjusted to activate the microswitch
on any position upon your needs.
To install this front mount microswitch:
No.
A
Place the valve into the position during which you need the signal.
Remove the cover and the controller.
B
See chapters 9.4.1. First steps, page 69, 9.4.7. Disassembling valve from tank, page 73 and
9.4.9. Optical sensor and controller replacement, page 75.
C
Screw switch base to top plate using the switch guide pin over screw boss.
Install the cam so that the microswitch pin is released and screw the cam using a self-
D
tapping screw.
E
Connect wires.
Hole
Guide pin
Ref. MKT-IM-021 / A - 20.02.2019
Installer Manual 255/LOGIX 742-762-764 - Description
Operation
Switch
Camshaft
Switch cam
17 / 92