4.2

Modulating control

The modulating positioning
signal drives the actuator
steplessly. The positioning
signal range
(DC 0...10 V / DC 4...20 mA,
0...1000 Ω) corresponds in a
linear manner to the positioning
range (fully closed...fully open,
or 0...100% stroke).
The actuator is driven via
connection terminal Y or forced
control Z (page 66). The
required stroke / rotation is
transferred to the valve's stem /
spindle.
Positioning
Stroke actuator
signal
Signal Y, Z
Actuator's stem
increasing
extends
Signal Y, Z
Actuator's stem
decreasing
retracts
Signal Y, Z
Actuator's stem
constant
maintains the position
· If function module AZX61.1 is used, observe the information given in chapter
"Changeover of acting direction" (page 59).
· Observe the information given in chapter "Acting direction and flow
characteristic" on page 61.
Actuators SAX.., SAY.., SAV.., SAL.. for valves
Functions and control
1
Calibration slot
2
LED (2 colors)
3
DIL switches
4
Function module
5
A/D conversion
6
Power supply
Control
7
functions
8
Brushless DC motor
9
Gear train
Manual adjuster
Rotary actuator
Actuator's spindle turns in
clockwise direction
Actuator's spindle turns in
counterclockwise direction
Actuator's spindle
maintains the position
Changeover of characteristic
Positioning signal
Identification of seat
Position control
Motor control
Detection of foreign bodies
Calibration
Forced control
Characteristics function
Manual adjustment
Control
Bypass
path valve
valve
AàAB
B à AB
Opening
Closing
Closing
Opening
Maintains the position