GBB/GIB16..1
Modulating control, fully
open, fully locked with
GBB/GIB16..1
Operating states with
GBB/GIB16..1
Note
Siemens
Smart Infrastructure
9.4
Connection diagrams (modulating)
9.4.1
Typical application
The controller output is connected directly to the actuator input.
SP
(G)
(Y)
1
8
S1
GBB/GIB16...
2
9
S2 S3
P
SN
9.4.2
Special diagram for modulating control
The following diagram enables enable different operating states of the actuator
depending on the position of the changeover switch with switch contacts K1, K2, K3
(see table of operating states).
SP
(G)
D
(Y)
K2
K1
K3
1
8
S1
GBB/GIB16...
2
9
S2 S3
P
SN
Switch
Operating state
contacts
Modulating control
K3
Fully open
K2
Fully closed
K1
Rotary direction switch
*) Full opening for actuator types with adjustable characteristic function depends on
the set voltage values (Uo,
Rotary actuators without spring return GBB/GIB..1
Diagrams
(G0)
N
S4
Y
S5 S6
(G0)
N
S4
Y
S5 S6
Direction of rotation
Factory setting
D
U) and the supply voltage tolerance.
N
Controller
Y
Actuator GBB/GIB16..1
P
Position indication
SP
System potential AC 24 V
SN
System neutral
N
Controller
Y
Actuator GBB/GIB16..1
P
Position indication
SP
System potential AC 24 V
SN
System neutral
D
Diode (e.g. R4000)
K1...K3 Switch contacts (10 V / 0.1 mA)
CE1Z4626en
39/44
2019-11-28