How To Configure The Redundancy Connection For Batch Servers On The Engineering Station - Siemens SIMATIC PCS 7 Function Manual

Fault-tolerant process control systems (v8.0)
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Advantages of fault-tolerant components
4.6 SIMATIC BATCH Stations
Requirements
● A network adapter for the local Ethernet network is available for redundancy monitoring on
● All software components have been installed on the BATCH servers.
Procedure
1. Open the dialog window "Network connections" via the Control Panel.
2. Select the menu command Advanced > Advanced Settings.
3. The terminal bus must be at the top of the list for the connections. Set the 3rd network
4. Deactivate the options "Client for Microsoft Networks" and "File and Printer Sharing ..." in
5. Click "OK".
6. In the "LAN or High-speed Internet" list of the "Network Connections" dialog box, select the
7. Check the "Internet Protocol (TCP/IP)" box and deactivate all other elements.
8. Select "Internet Protocol (TCP/IP)".
9. Click "Properties".
10.Set the "local" IP address in the "General" tab.
11.Click "OK".
4.6.5
How to configure the redundancy connection for BATCH servers on the engineering
station
Introduction
Additional tasks must be performed in the engineering and for setting up the PC stations for
redundant BATCH servers:
● On the engineering station:
● On each BATCH server:
154
each BATCH server of a server pair (referred to below as the 3rd network adapter).
adapter in the list under the terminal bus.
the "Network Adapters and Bindings" tab for the 3rd network adapter.
3rd network adapter and then select the menu command File > Properties.
The "Properties of Internet Protocol (TCP/IP)" dialog box opens.
Note
Enter different IP addresses for the master server and standby server from a private
subnet range (e.g., subnet 192.168.0.0) that cannot be routed to the WAN.
Check the default engineering settings in effect
Set the network adapter for redundancy monitoring
Fault-tolerant Process Control Systems (V8.0)
Function Manual, 03/2012, A5E02779471-02