8. In the "Select the adapters to include in this team" list, select the network adapters through
9. Click "Next".
10.In the "Select a team type" list, select "SFT (Switch fault tolerance)". Click "Next".
11.Click "Finish".
12.The "Properties of team: <team name>" dialog box opens ("TerminalBusTeam #0" in the
13.Select the "Settings" tab and click "Modify Team...".
14.In the "Adapters" tab, select network adapter 1 on the preferred terminal bus.
15.Select the "network adapter 2" on the redundant terminal bus. Click "Set Secondary".
16.Click "OK" to confirm the Team dialog boxes.
17.The Team dialog boxes close.
18.Open the dialog window "Network connections" ("Change adapter settings") via the control
19.If the entry "File" is missing in the menu bar, select the menu command Organize > Layout
20.Activate the detailed view of the list.
21.Check the order of network adapters under "Advanced> "Advanced Settings ...". In the
22.Click "OK" to close the dialog box.
Fault-tolerant Process Control Systems (V8.0)
Function Manual, 03/2012, A5E02779471-02
which the computer should be connected to the redundant terminal bus.
– "Network adapter 1" (see table)
– "Network adapter 2" (see table; INTEL Desktop Adapter or L adapter for the INTEL
onboard network adapters)
The "New Team Wizard" dialog box closes.
The team ("TerminalBusTeam #0" in the example) is entered in the "Settings" dialog box
of the network adapter.
example).
Click "Set Primary".
The two network adapters are entered as a team in the Device Manager
(Example: Team: Intel (R) Pro/1000 ...).
panel.
> Menu bar.
Recommendation: Allocate names to the network adapters (File > Rename)
Example:
– 1. <Team name> <Team> ("TerminalBusTeam #0" in the example)
– 2. <Team name> <Master> ("TerminalBusTeam #0 (Master)" in the example)
– 3. <Team name> <Standby> ("TerminalBusTeam #0 (Standby)" in the example)
"Adapters and Connections" tab, the team must be at the top of the list under "Connections":
– 1. <Team name>" (in the example, "TerminalBusTeam #0")
– 2. <Team name> <Master ... Adapter> (INTEL server adapter or LM adapter for INTEL
onboard network adapters)
– 3. <Teamname> <Standby ... Adapter> (INTEL desktop adapter or L adapter for INTEL
onboard network adapters)
Advantages of fault-tolerant components
4.3 Communication connections
99