S1 - Threshold Switch - Siemens SINAMICS S120 Equipment Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Note
Applying a high signal level to "DI inhibit input" inhibits the Braking Module. On a falling
edge, pending error messages are acknowledged.
The "DO fault output" signal can be used for evaluation in the Control Unit.
On the "+24 V" signal, 24 V DC must be provided by the customer to supply the Braking
Module.
8.27.3

S1 - Threshold switch

The response threshold at which the Braking Module is activated and the DC link voltage
generated during braking is specified in the following table.
The threshold switch position may be changed only when the Basic Line, Smart Line,
Active Line, or Motor Module are switched off and the DC link capacitors are discharged.
Table 8- 34
Response thresholds of the Braking Modules
Rated voltage
Response
threshold
380 ... 480 V
673 V
774 V
500 ... 600 V
841 V
967 V
660 ... 690 V
1070 V
1158 V
S120 Cabinet Modules Equipment Manual
Manual, (GH5), 10/2008, A5E00427098A
WARNING
Switch
Comments
position
1
774 V is the default factory setting. With line voltages of between 380 and
400 V, the response threshold can be set to 673 V to reduce the voltage
2
stress on the motor and converter. This does, however, reduce the possible
braking power with the square of the voltage (673/774)² = 0.75.
The maximum possible braking power is, therefore, 75%.
1
967 V is the default factory setting. With a line voltage of 500 V, the response
threshold can be set to 841 V to reduce the voltage stress on the motor and
2
converter. This does, however, reduce the possible braking power with the
square of the voltage (841/967)² = 0.75.
The maximum possible braking power is, therefore, 75%.
1
1158 V is the default factory setting. With a line voltage of 660 V, the
response threshold can be set to 1070 V to reduce the voltage stress on the
2
motor and converter. This does, however, reduce the possible braking power
with the square of the voltage (1,070/1,158)² = 0.85.
The maximum possible braking power is, therefore, 85%.