Cabinet Modules
5.6 Motor Modules in chassis format
Minimum cable lengths for parallel connection and connection to a motor with a single-winding
system
NOTICE
The minimum motor cable lengths specified in the table below must be observed when two
or more Motor Modules are connected in parallel and there is a connection to a motor with
a single-winding system. If the cable length required cannot be achieved in the application,
provision must be made for a motor reactor (option L08).
Table 5- 44
Frame size
FX
FX
GX
GX
GX
HX
HX
HX
JX
JX
JX
Table 5- 45
Frame size
FX
FX
FX
FX
GX
GX
GX
GX
HX
HX
HX
JX
JX
JX
JX
JX
184
Motor Modules, 510 ... 720 V DC
P
[kW]
rated
110
132
160
200
250
315
400
450
560
710
800
Motor Modules, 675 ...1035 V DC
P
[kW]
rated
75
90
110
132
160
200
250
315
400
450
560
710
800
900
1000
1200
I
[A]
rated rms
210
260
310
380
490
605
745
840
985
1260
1405
I
[A]
rated rms
85
100
120
150
175
215
260
330
410
465
575
735
810
910
1025
1270
S120 Cabinet Modules Equipment Manual
Manual, (GH5), 10/2008, A5E00427098A
Minimum length [m]
30
27
20
17
15
13
10
9
8
6
5
Minimum length [m]
100
90
80
70
60
50
40
30
25
25
20
18
15
12
10
8