Maintenance and servicing
6.4 Replacing components
Note
Frame size HX contains two DC fuses and frame size JX four DC fuses.
If you order a complete power unit as a replacement, make sure that only DC fuses are
used. If option L37 (DC interface with pre-charging input circuit) is installed in your cabinet,
the DC fuses of the spare part must be replaced with the lugs of the existing power unit.
6.4.11.5
Replacing the DC fuses for Motor Module in chassis format, frame sizes HX and JX
Replacing the DC fuses
Figure 6-29
Preparatory steps
● Observe the "five safety rules".
● Disconnect the cabinet from the power supply (do not forget the external power supplies).
● Remove the protective cover.
● Allow unimpeded access.
The DC voltage may still be present for up to 5 minutes.
302
Replacing the DC fuses, frame sizes HX and JX
CAUTION
S120 Cabinet Modules Equipment Manual
Manual, (GH5), 10/2008, A5E00427098A