Commissioning
13.4 Setting the motor protection function
You can set different CLASS characteristics according to the startup class. If the
potentiometer is set to OFF, the "electronic motor overload protection" function is
deactivated.
Note
The rated data of the soft starters refers to normal starting (CLASS 10). The starters may
need to be calculated with a size allowance for heavy-duty starting (> CLASS 10). You can
only set a rated motor current that is lower than the soft starter rated current (refer to chapter
Motor current settings (Page 120)); if not, a fault will be indicated by the OVERLOAD LED
(red flashing ) and it will not be possible to start the SIRIUS 3RW soft starter.
13.4.2

Motor current settings

3RW4024-...
3RW4026-...
3RW4027-...
3RW4028-...
3RW4036-...
3RW4037-...
3RW4038-...
3RW4046-...
3RW4047-...
3RW4055-...
3RW4056-...
3RW4073-...
3RW4074-...
3RW4075-...
3RW4076-...
13.4.3

Motor protection acc. to ATEX

Refer to the information in chapter Motor protection / intrinsic device protection (3RW40 only)
(Page 42).
120
I
[A]
I
[A]
I
[A] CLASS 10
e
min
max
12.5
5
12.5
25.3
10.3
25.3
32.2
17.2
32.2
38
23
38
45
22.5
45
63
25.5
63
72
34.5
72
80
42.5
80
106
46
106
134
59
134
162
87
162
230
80
230
280
130
280
356
131
356
432
207
432
I
[A] CLASS 15
I
max
max
11
10
23
21
30
27
34
31
42
38
50
46
56
50
70
64
84
77
134
124
152
142
210
200
250
230
341
311
402
372
SIRIUS 3RW30 / 3RW40