3Rw402 - 3Rw404 And Dahlander Motor Starting - Siemens SIRIUS 3RW30 Manual

Industrial controls
Hide thumbs Also See for SIRIUS 3RW30:
Table of Contents

Advertisement

Typical circuit diagrams
16.11 Dahlander / multispeed motor
16.11.2

3RW402 - 3RW404 and Dahlander motor starting

Figure 16-33 Wiring of the 3RW402 - 3RW404 control circuit and 3RW402 - 3RW407 main circuit
(1) For permissible main and control voltage values (dependent on article number), refer to
chapter Technical data (Page 127).
(2) Automatic restart. Can result in death, serious injury, or property damage.
The start command (e.g. issued by the PLC or switch S1) must be reset prior to issuing a
RESET command because the motor attempts to restart again automatically following this
RESET command if a start command is still present. This particularly applies if the motor
protection has tripped. For safety reasons, you are advised to integrate the group fault
output (terminals 95 and 96) in the controller.
194
WARNING
SIRIUS 3RW30 / 3RW40
Manual, 10/2018, NEB535199502000/RS-AB/005

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sirius 3rw40

Table of Contents