Adjustment Elements - Siemens FS20 Mounting & Installation

Fire detection system
Table of Contents

Advertisement

Mounting and installation of the compact control panels
5
Operating add-on with 20 zones EVAC-NL [NL]

5.34.1 Adjustment elements

226 | 354
Building Technologies
Fire Safety
The EVAC-NL indicator is configured with the switch S20.
Setting for one or the first EVAC-NL
Switch S20
1
2
3
4
S0
S1
S2
Master Syn (Empty)
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
X
X
X
ON
Blank fields = Switch in 'OFF' position
X = Switch position according to addresses 1 to 5
If working with a single EVAC-NL indicator (10 zones) and if working with the first
1
EVAC-NL indicator, S20/4 (Master) must always be set to ON. If used in the EVAC-
NL mimic display driver, the S20/5 (Syn) switch must also be ON.
Each address can be assigned only once per ↑ station.
The factory setting is always made for the application in question.
Meaning
5
6
OFF
Device address 1
OFF
Device address 2
OFF
Device address 3
OFF
Device address 4
OFF
Device address 5
ON
Mimic display outputs are actuated
and polled (LED, keys and key switch)
1
008851_s_en_--
2016-01-27