Figure 3.2 - Attach inner assembly to flue collar.
Assemble Slip Sections
The outer flue of the slip section should slide over the outer
flue of the pipe section and into (inner flue) the last pipe
section, Figure 3.4.
ST647
Slide together to the desired length, making sure that a 1-1/2"
attach inner assy
outer flue overlap is maintained between the pipe section
and slip section.
The pipe and slip section need to be secured by driving two
1/2 in. screws through the overlapping portions of the outer
flues using the pilot holes, Figure 3.5.
This will secure the slip section to the desired length and
prevent it from separating. The slip section can then be
attached to the next pipe section.
If the slip section is too long, the inner and outer flues of the
slip section can be cut to the desired length.
!
Risk of Fire/Explosion! DO NOT break seals on slip
sections. Use care when removing termination cap from
slip pipe. If slip section seals are broken during removal
of the termination cap, vent may leak.
CORRECT
Figure 3.3 - Make sure the seams are not aligned to prevent
unintentional disconnection.
1616
SLP
CCSLP
WARNING
INCORRECT
Vermont Castings • Radiance RADVT Installation Manual_R4 • 04/19
Figure 3.4 - Slip Section Pilot Holes
Figure 3.5 - Screws into Slip Section
Secure the Vent Sections
Vertical sections of SLP pipe must be supported every 8 feet.
The SLP firestop includes tabs that may be used to secure
vertical sections.
The vent support or plumber's strap (spaced 120° apart) may
be used to secure the vertical sections of pipe, Figure 3.6.
Horizontal sections of vent must be supported every 5 feet
with a vent support or plumber's strap, Figure 3.7.