Vermont Castings Radiance RADVT Series Installation & Operating Manual page 20

Direct vent gas heater
Table of Contents

Advertisement

Wall Screws
and Anchors
Snorkel
Termination Cap
12"
Clearance
Gravel
Drain
Window Well
Figure 3.16 - Snorkel kit installation.
Vertical Through-The-Roof Application/Installation:
Note: Refer to Figures 2.8 thru 2.10 for restrictor plate
adjustments for vertical vent runs.
This gas stove has been approved for:
• Vertical installations up to 40 feet (12 m) in height. Up to
a 10 feet (3 m) horizontal vent run can be installed within
the vent system using a maximum of two 90° elbows,
Figure 3.17.
• Up to two 45° elbows may be used within the horizontal
run. For each 45° elbow used on the horizontal plane,
the maximum horizontal length must be reduced by 18"
(450 mm).
Example: Maximum horizontal length:
No elbows
= 10' (3 m)
1 x 45° elbow = 8.5' (2.6 m)
2 x 45° elbows = 7' (2.1 m)
• A minimum of an 8 feet (2.5 m) vertical rise is required,
Figure 3.17.
• Two sets of 45° elbow offsets may be used within the
vertical sections. From 0 to a maximum of 8 feet (2.5 m)
of vent pipe can be used between elbows, Figure 3.17.
• SLP-HVS supports offsets. This application will require
that you first determine the roof pitch and use the
appropriate starter kit. (Refer to Venting Components
list.)
• The maximum angular variation allowed in the system is
270°, Figure 3.18
• For the minimum height of the vent above the highest
point of penetration through the roof, Figure 3.18.
2020
Waterproof Seal
Around Pipe
Firestop
RADIANCE
ST653
install snorkel
04/19 ts
Vermont Castings • Radiance RADVT Installation Manual_R4 • 04/19
Vertical Termination
Storm Collar
Flashing
Firestop
Spacer
Ceiling
Support
Plate
Figure 3.17 - Typical Vertical Venting Configuration
ST933
Selkirk vertical venting
6/07
Offset
Support Collar
Ceiling Support Collar
Trim Plate
3-90-30007498