Advertisement

5.
In Step 5 – Summary, check parameter values. Click BACK to return and revise
values, or FINISH to transfer values to the device.
The message Quick Setup was successful will appear. Click OK.

Configuring a stillpipe application

Launch the Quick Start wizard and follow steps 1 to 2.
In step 2, select Application Type – Level in a vessel with stillpipe; Material – Liquid
Low dK; and set the stillpipe diameter as desired. The propagation factor is
automatically updated according to the pipe diameter.
Continue through steps 3 to 5 then click on Transfer to download settings to the
device.
Page 36
SITRANS LR200 (PROFIBUS PA) – INSTRUCTION MANUAL
7ML19985JR01