Horizontal vessel with volume measurement

Notes:
• The minimum distance from the flange face to the target is limited by Near Range
(2.2.3.5.1.).
• We recommend adjusting Auto False Echo Suppression (2.2.4.2.) with an empty
or almost empty vessel.
The application is to obtain a level measurement proportional to vessel volume in a
chemical vessel.
Low Calibration Point is the bottom of the tank (3.5 m/11.48 ft from the sensor
reference point).
High Calibration Point is 0.5 m (1.64 ft) from the sensor reference point. The
maximum rate of filling or emptying is about 0.2 m/min.
Select PARABOLIC ENDS in Vessel Shape (2.2.2.2.) then enter values for
,
(2.2.2.3.)
Dimension A (2.2.2.4.), and Dimension L (2.2.2.5.)
of level.
In the event of a loss of echo, after 2 minutes the device is to report a user-defined
value of 3.25 m (Fail-safe High condition).
Sensor
reference
point
0.5 m
3.5 m
High
Cal.
Point
Low
Cal.
Point
NOTE: Table continues on next page.
Parameter
Parameter Name
type
(number)
Material (1.1.)
Response Rate (1.2.)
Units (1.3.)
Quick start
wizard
Operation (1.4.)
parameters
Low Calibration Point (1.5.)
High Calibration Point (1.6.)
Apply? (Apply changes) (1.7.)
7ML19985JR01
SITRANS LR200 (PROFIBUS PA) – INSTRUCTION MANUAL
A
to get a volume reading in place
L
Value
Function
LIQUID
MED
1 m/minute
M
meters
Volume replaces Level
when a vessel shape is
LEVEL
selected in Vessel Shape
(2.2.2.2.)
5
5 m
0.5
0.5 m
YES
Max Volume
100% =
8000 liters
Volume
reading
A
Page 117