1.5. Low Calibration Point (LOW CALIB. PT.)
Distance from Sensor Reference to Low Calibration Point: usually process empty level. See
Operation (1.4.) for an illustration.
Range: 0.0000 to 30.000 m
Values
1.6. High Calibration Point (HIGH CALIB. PT.)
Distance from Sensor Reference to High Calibration Point: usually process full level. See
Operation (1.4.) for an illustration
Range: 0.0000 to 30.000 m
Values
1.7. Apply changes (APPLY?)
To save the Quick Start settings it is necessary to select Yes to apply changes.
Options
Press Mode
to return to Measurement mode. SITRANS LR260 is now ready to operate.
: For liquid applications, some parameters must be modified following the Quick Start
Note
Wizard. See full Operating Instructions for details.

Communications via PROFIBUS PA

Notes:
• The following instructions assume that the user is familiar with PROFIBUS PA.
• You will need the full Operating Instructions to acquire the list of applicable parameters.
Configuring the PROFIBUS PA master
To configure SITRANS LR260 on the network, you will need the GSD file SIEM8162.gsd. You can
download the file from the product page of our web site. Go to: www.siemens.com/LR260 and
click on Downloads.

SIMATIC PDM

• We recommend that you use SIMATIC Process Device Manager (PDM) to program your
device. Please consult the operating instructions or online help for details on using
SIMATIC PDM.
• You can find more information at www.fielddevices.com: go to Products and Solutions >
Products and Systems > Communications and Software > Process Device Manager.
Device Description (EDD)
SITRANS LR260 requires the EDD for SIMATIC PDM version 6.0 with SP3 or higher.
Note:
• You can locate the EDD in Device Catalog, under Sensors/Level/Echo/Siemens
Milltronics/SITRANS LR260.
• Check the product page of our website at: www.siemens.com/LR260, under Downloads,
to make sure you have the latest version of SIMATIC PDM, the most recent Service Pack
(SP) and the most recent hot fix (HF).
• If necessary download the EDD, save the files to your computer, and extract the zipped
file to an easily accessed location.
A5E32114443
SITRANS LR260 (PROFIBUS PA) – QUICK START MANUAL
.
YES, NO, DONE (Display shows DONE when Quick Start is successfully
completed)
Page EN-17