Horizontal vessel with volume measurement

Note:
The minimum distance from the flange face to the target is limited by Near Range
(2.5.1.).
To obtain level measurement proportional to vessel volume in a chemical vessel:
Low Calibration Point = 3.5 m (11.48 ft) from sensor reference point
High Calibration Point = 0.5 m (1.64 ft) from sensor reference point.
Max. fill/empty rate = 0.2 m/min. (0.65 ft/min.)
Select vessel shape, Parabolic Ends, and enter values for A and L, to obtain a volume reading
instead of level.
In the event of a loss of echo: SITRANS LR250 is to report a status of BAD or UNCERTAIN
after 120 seconds (2 minutes).
sensor
reference
0.5 m
point
High
Cal
Point
3.5 m
Low Cal
Point
Parameter
Parameter Name
type
Introduction
Language
Material
Quick Start
Response Rate
Wizard
Units
parameters
Low Calibration Point
High Calibration Point
Wizard Complete
Vessel Shape (2.4. 1 .1.)
PV (volume/level) Units
(2.3.3.)
Indepen-
Level Unit (2.3.2.)
dent
Maximum Volume (2.4.1.2.)
parameters
Dimension A (2.4.1.3.)
Dimension L (2.4. 1 .4.)
Loss of Echo (LOE) Timer
(2.3.6.)
Return to Measurement: press Mode
7ML19985JKL1
A
= 0.8 m
to start normal operation.
SITRANS LR250 (FF) – OPERATING INSTRUCTIONS
L
= 6 m
Options/Values Function
NEXT
Continue with Wizard.
NEXT
Continue with current language.
LIQUID
MED
Medium =1 m/minute
M
meters
3.5
3.5 m (11.48 ft)
0.5
0.5 m (1.64 ft)
Transfers Quick Start settings to
FINISH
device.
PARABOLIC ENDS
Defines vessel shape.
L
litres
M
meters
8000
8000 liters
0.8
0.8 m (2.62 ft)
6
6 m (19.68 ft)
120
120 seconds
100% = 8000 l
volume
reading
A
= 0.8 m
Page 157