Connecting
5.2 Ports
5.2.3

Connectors of the digital inputs of the SCALANCE X414-3E

Polarity reversal protection X1, X2
The two 5-pin male connectors (X1, X2) of the digital inputs 1 through 8 have no polarity
reversal protection. If the connectors are accidentally swapped over, this does not cause
damage or destroy circuits. In display modes A and C or B and D, incorrect inputs are
displayed during the time the connectors are swapped over.
The input voltage must not exceed + 30 V and must not fall below – 30 V, otherwise the DI
module will be destroyed.
Connectors of the digital inputs 1 to 4 on male connector X1
Digital inputs 1 through 4 are connected using a 5-pin connector at the front terminal block
on the DI module.
Figure 5-3
Conn. 1
104
WARNING
Pins of connector X1 (inputs 1-4)
IN1
IN2
M4
IN3
IN4
Digital input 1
Digital input 2
Ground
Digital input 3
Digital input 4