General Specifications; Common Specifications - Mitsubishi FR-S520-*K Series Manual

Table of Contents

Advertisement

General Specifications

Specifications
Type
Applicable motor capacity (kW) (Note 1)
Rated capacity (kVA)(Note 2)
Rated current (A)
Output
Overload current rating (Note 3)
Voltage (Note 4)(Note 6)
Rated input AC voltage/frequency
Tolerable AC voltage fluctuation
Power supply
Tolerable frequency fluctuation
Power facility capacity (kVA)(Note 5)
Protective structure (JEM 1030)
Cooling method
Approximately weight (kg)
1. The applicable motor indicates the maximum applicable capacity when using a Mitsubishi standard 4-pole motor.
(Notes)
2. The rated output capacity is 230V for the 3-phase 200V output voltage, and 440V for the 3-phase 400V output voltage.
3. The overload current rating percentage indicates the percentage in respect to the inverter's rated output current. When used repeatedly, it is necessary to wait for the inverter motor to return to a temperature
less than the temperature for the 100% load.
4. The maximum output voltage will not exceed the power supply voltage for the 3-phase 200V/400V power input specification product and the single-phase 200V power input specification product. The
single-phase 100V power input specification product cannot output more than twice the power voltage.
5. The power capacity will change according to the power side impedance (including the input reactor or wire) values.
6. For the single-phase 100V power input specification product, when a load is applied on the motor, the output voltage will drop by approx. 10 to 15%. However, when using a general-purpose motor, the
load must be reduced before use.

Common Specifications

Control method
Output frequency range
Frequency setting resolution
Frequency precision
Starting torque
Acceleration/deceleration time setting
Regenerative (Note 1)
Braking torque
DC braking
Input signals
Operation functions
Operation functions
For meter
Protection and warning functions
Ambient temperature and humidity
Storage temperature (Note 3)
Atmosphere
Altitude and vibration
(Notes)
1. The indicated braking toque is the short-term average torque (which changes with motor loss) when the motor alone is decelerated from 60Hz. It is not the continuous regenerative torque. Deceleration
from frequencies exceeding the base frequency will have a lower average deceleration torque value.
2. If an undervotlage occurs, an error will not be output, but the output will be cutoff. Operation can be resumed after restoring the power, but depending on the operation state (size of load, etc.), the overcur-
rent protection or regenerative overvoltage protection may function when the power is restored.
3. This is the temperature to which units can be exposed for a short time, such as during transportation.
4. This corresponds only to the products with built-in cooling fan.
5. This applies only to the type with RS-485 function.
6. This functions only when the external thermal input (OH) is selected with Pr. 60 to Pr. 63 (input terminal function selection).
7. This functions only when Pr. 40 (start-time ground fault detection selection) is set to 1.
4
3-phase 200V
FR-S520-
0.1K
0.2K
0.4K
0.75K
1.5K
2.2K
0.1
0.2
0.4
0.75
1.5
2.2
0.3
0.5
1.0
1.6
2.8
4.0
0.8
1.4
2.5
4.1
7.0
10
3-phase 200 to 240V, 50/60 Hz
3-phase 200 to 240V, 50/60 Hz
170 to 264V, 50/60Hz
0.4
0.7
1.2
2.1
4.0
5.5
Enclosed type (IP20) (Fully enclosed structure series is IP40)
Self-cooling
Forced cooling
0.5
0.5
0.8
0.9
1.5
1.5
Select from V/F control (Soft-PWM control/high carrier frequency PWM control selective) and automatic torque boost control
0.5 to 120Hz (starting frequency can be varied between 0 and 60Hz)
5VDC input: 1/500 of maximum setting frequency, 10VDC, DC4 to 20mA input: 1/1000 of maximum setting frequency
Digital input: 0.1Hz (less than 100Hz), 1Hz (100Hz or more)
Analog input: Within
1% of maximum output frequency (25˚C
Digital input: Within
0.5% of set output frequency (when setting dial is used)
150% (at 6Hz) during automatic torque boost control
0,0.1 to 999 s (acceleration/deceleration can be set individually), linear or S-pattern acceleration/deceleration mode can be selected
0.1K, 0.2K,
150%, 0.4K, 0.75K,
Operation frequency (0 to 120Hz), operation time (0 to 10 seconds), operation voltage (0 to 15%)
Frequency setting signal (0 to 5 (10)VDC), 4 to 20mA, digital setting with setting dial, start signal, error reset (RES), multi-speed selection
(RL, RM, RH, REX), 2nd function selection (RT), output stop (MRS), current input selection (AU), external thermal input (OH), start self-
hold selection (STOP), JOG mode selection (JOG), PID action selection (X14), PU operation/external operation changeover (X16)
Upper/lower limit frequency setting, frequency jump operation, external thermal input selection, restart after instantaneous power failure,
forward/reverse run prevention, slip compensation, operation mode selection, PID control, computer link operation (RS-485) (Note 5)
One type of open collector output can be selected from inverter running (RUN), frequency reached (SU), frequency detection (FU), overload
warning (OL), zero current detection (Y13), output current detection (Y12), PID upper limit (FUP), PID lower limit (FDN), PID forward/
reverse run (RL), READY (RY), minor failure (LF), and error (A, B, C). One type can be selected for the contact output (1 contact, 230VAC 0.3A, 30VDC 0.3A).
One type can be selected from output frequency or motor current. Pulse train output (1440 pulse/s 1mA full scale).
Overcurrent cutoff (during acceleration, deceleration, and constant speed), regenerative overvoltage cutoff (during acceleration,
deceleration, and constant speed), overload cutoff (electronic thermal relay), fin overheating, fan trouble (Note 4), stall prevention,
output side ground fault protection at starting (Note 7), external thermal input (Note 6), PU dislocation (Note 5), No. of retries exceeded,
communication error (Note 5), CPU error, undervoltage (Note 2)
–10˚C to + 50˚C(non freezing), (–10˚C to + 40˚C for fully enclosed structure specifications), 90%RH or less(non condensing)
–10˚C to + 65˚C
Indoors with no corrosive gases, flammable gases, oil mist or dust
1000m or less above sea level, 5.9m/s
3-phase 400V
FR-S540-
3.7K
0.4K
0.75K
1.5K
2.2K
3.7K
3.7
0.4
0.75
1.5
2.2
3.7
6.6
0.9
1.6
2.7
3.7
5.9
16.5
1.1
2.1
3.5
4.8
7.7
150% for 60 s, 200% for 0.5 s (Inverse time characteristics)
3-phase 380V to 480V, 50/60 Hz
3-phase 380V to 480V, 50/60 Hz
325V to 528V, 50/60Hz
Within
5%
9
1.5
2.5
4.5
5.5
9.5
Self-cooling
Forced cooling
2.1
1.5
1.5
1.5
1.6
1.7
10˚C)
100%, 1.5K,
50%, 2.2K 3.7K 20%
2
or less (JIS C 0040 compliant)
Single-phase 200V
Single-phase 100V
FR-S520S-
0.1K
0.2K
0.4K
0.75K
1.5K
0.1K
0.1
0.2
0.4
0.75
1.5
0.1
0.3
0.5
1.0
1.6
2.8
0.3
0.8
1.4
2.5
4.1
7.0
0.8
3-phase 200 to 240V, 50/60 Hz
3-phase 200V to 230V, 50/60Hz
Single-phase 200 to 240V, 50/60Hz
Single-phase 100V to115V, 50/60Hz
170 to 264V, 50/60Hz
90V to 132V, 50/60Hz
0.5
0.9
1.5
2.5
4.4
0.5
Enclosed type ( IP20 )
Self-cooling
Forced cooling
0.5
0.6
0.8
1.0
1.5
0.6
FR-S510W-
0.2K
0.4K
0.75K
0.2
0.4
0.75
0.5
1.0
1.6
1.4
2.5
4.1
0.9
1.5
2.5
Self-cooling
0.7
0.9
1.6

Hide quick links: