Dm Allocations - Omron SYSMAC C Series Operation Manual

Analog i/o units
Hide thumbs Also See for SYSMAC C Series:
Table of Contents

Advertisement

Two-word Operation

4-3-3 DM Allocations

Data Writing Area
Point
DM word
0
DM m
1
DM m+1
2
DM m+2
3
DM m+3
4
DM m+4
5
DM m+5
6
DM m+6
7
DM m+7
8
DM m+8
9
DM m+9
10
DM m+10
11
DM m+11
12
DM m+12
13
DM m+13
14
DM m+14
15
DM m+15
16
DM m+16
17
DM m+17
18
DM m+18
19
DM m+19
20
DM m+20
21
DM m+21
22
DM m+22
23
DM m+23
24
DM m+24
25
DM m+25
!
Caution
40
The I/O WRITE Instruction (WRIT) is used to transfer a maximum of 26 words of
data to the Analog Input Unit.
The following applies if mean value and scaling are not used together.
All Input Points Used:
Some Input Points Unused:Transfer the data set in DM 0000 and DM 0001 to
15
14
13
12
11
Specify points for mean function
Specify points for scaling function
Mean value 1
Mean value 2
Mean value 3
Mean value 4
Mean value 5
Mean value 6
Mean value 7
Mean value 8
Scaling offset 1
Scaling gain 1
Scaling offset 2
Scaling gain 2
Scaling offset 3
Scaling gain 3
Scaling offset 4
Scaling gain 4
Scaling offset 5
Scaling gain 5
Scaling offset 6
Scaling gain 6
Scaling offset 7
Scaling gain 7
Scaling offset 8
Scaling gain 8
Input the mean value and scaling values only for points for which the mean
and/or scaling function has been designated. If one of these is not needed for a
point, move all other parameters up one word to replace it. For example, if a
mean value is not required for input point 3 but is required for points 1, 2, and 4,
the mean value for point 4 would be placed in DM m+ 4 instead of DM m+5.
No setting of WRIT data required. Use without
changing the settings.
the Analog Input Unit with the WRIT instruction.
Bit
10
9
8
7
6
Specify points to be used
0
Section 4-3
5
4
3
2
1
0
0