Omron SYSMAC C Series Operation Manual page 61

Analog i/o units
Hide thumbs Also See for SYSMAC C Series:
Table of Contents

Advertisement

Two-word Operation
Ladder Programming Example Using C1000H
First Scan Flag
25315
First Scan Flag
25315
07000
25506
(Continued on next page.)
MOV(21)
MOV(21)
MOV(21)
MOV(21)
MOV(21)
MOV(21)
MOV(21)
MOV(21)
MOV(21)
MOV(21)
WRIT(87)
(EQ)
Specifies the points to
be used and mean val-
#F0FF
ue settings.
DM0000
Specifies scaling set-
#C000
tings.
DM0001
Input point 5
(5 samples)
#0005
DM0002
Input point 6
(10 samples)
Sets the
#0010
mean
DM0003
data
(sampling
Input point 7
counts).
(20 samples)
#0020
DM0004
Input point 8
(50 samples)
#0050
DM0005
Input point 7
offset data
#0000
DM0006
Input point 7
gain data
Sets the
#3000
scaling
DM0007
data.
Input point 8
offset data
#1000
DM0008
Input point 8
gain data
#5000
DM0009
Transfers the 10 words of parameters from
#0010
DM 0000 through DM 0009 to the Analog
DM0000
Input Unit.
000
When the transfer is complete, SR
07000
25506 (the Equal Flags) turns ON.
Here, IR 07000 is used as a work bit to
hold the status of EQ at this point.
Section 4-3
These settings
can be made via
the Programming
Console using
data modification
functions instead
of in program-
ming, if desired.
45