Wiring - Omron SYSMAC C Series Operation Manual

Analog i/o units
Hide thumbs Also See for SYSMAC C Series:
Table of Contents

Advertisement

Settings and Wiring

9-2-4 Wiring

Current output
4 to 20 mA
or
0 to 20 mA
External Power Supply
The terminal arrangement is as shown in the following diagram.
External 24 V +
External 0 V
None
Output 1 +
Output 1 –
Output 2 +
Output 2 –
:
Output 3 +
Output 3 –
Output 4 +
Output 4 –
Output 5 +
Output 5 –
Output 6 +
Output 6 –
Output 7 +
Output 7 –
Output 8 +
Output 8 –
This Analog Output Unit must receive an external power supply of 24 VDC ±5%.
The current consumption is 0.8 A.
24 VDC
Note The external power supply to be used must meet the following specifications.
Output voltage: 24 V
Voltage adjustment range: ±5% min.
Constant-voltage output accuracy: ±3% max.
Output ripple: 400 mV
Current capacity: 1 A min. per Unit
When using the external power supply, adjust the output voltage between A0 and A1 or
between B0 and B1 to 24 ±0.3 V.
External 24 V +
External 0 V
None
Output 1 +
Output 1 –
Output 2 +
Output 2 –
Output 3 +
Voltage output
0 to 10 V
Output 3 –
0 to 5 V
Output 4 +
–5 to 5 V
or
Output 4 –
–10 to 10 V
Output 5 +
Output 5 –
Output 6 +
Output 6 –
Output 7 +
Output 7 –
Output 8 +
Output 8 –
or
max.
p-p
Section
9-2
:
24 VDC
151