Wolf WRS-K Installation And Operating Instructions Manual page 60

Regulatory system
Table of Contents

Advertisement

Alarm messages
Outside temp sensor faulty
or not connected (AL26)
Icing-up sensor HR faulty
or not connected (AL28)
Fire damper no. 1
responded (AL29)
Fault, EC motor, ventilation
fan (AL50)
Fault, EC motor, extract fan
(AL51)
KLM-E address 1 (AL52)
databus fault
KLM-E address 2 (AL53)
databus fault
KLM-E address 3 (AL54)
databus fault
KLM-E address 4 (AL55)
databus fault
KLM-E address 5 (AL56)
databus fault
Remote control not
connected or databus fault
(AL57)
Set value transd. not
or incorrectly connected
(AL58)
Service required (AL59)
Fault, heat recovery (AL61) Heat recovery
Humidifier service (AL62)
Humidifier fault (AL63)
60
14. Fault messages
Effects
Cause
Message only;
Sensor or lead faulty
special function
(night ventilation,
etc.) disabled
Heat recovery
Sensor or lead faulty
switched off or
does not control
Subject to parameter
An external building fire
settings, either
protection system has
system off, message
responded. Personnel
only or smoke
at risk from fire!
extraction
The system shuts
Fault recognition
down
through EC motor;
EC motor faulty
The system shuts
Fault recognition
down
through EC motor;
EC motor faulty
The system shuts
Extension module
down
faulty; BUS cable faulty;
incorrectly addressed
The system shuts
Extension module
down
faulty; BUS cable faulty;
incorrectly addressed
The system shuts
Extension module
down
faulty; BUS cable faulty;
incorrectly addressed
The system shuts
Extension module
down
faulty; BUS cable faulty;
incorrectly addressed
The system shuts
Extension module
down
faulty; BUS cable faulty;
incorrectly addressed
Remote control
Remote control
disabled
not connected or
databus fault
Set value transducer
Set value transducer
disabled
not or incorrectly
connected
Display only
Component hours run
exceeded
Heat recovery system
switched off or
faulty
does not control
Message only
Humidifier requires a
service
Humidifier shuts
Fault recognition
down; system
through humidifier;
continues to operate
humidifier faulty
Remedy
Check sensor and lead,
acknowledge fault message
Check sensor and lead
Reactivate fallen dampers,
acknowledge fault message
Check EC motor; acknowledge
fault message
Check EC motor; acknowledge
fault message
Check cable and address;
change extension module,
acknowledge fault message
Check cable and address;
change extension module,
acknowledge fault message
Check cable and address;
change extension module,
acknowledge fault message
Check cable and address;
change extension module,
acknowledge fault message
Check cable and address;
change extension module,
acknowledge fault message
Check remote control and
its wiring
Check set value transducer
and its wiring
Service the corresponding
components, reset operating
hours or increase limit value for
next service.
Check system; acknowledge
fault message
Service humidifier,
acknowledge fault message
Check humidifier; acknowledge
fault message
3062878_201707

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

KlmBmkBmf

Table of Contents