Parameter setting list for
"Humidity control"
46
10. Operating level 2
Parameter
Prop. fresh air for
hygrostat function
Fan stage for
hygrostat function
Fan speed for
hygrostat function
Continuous hygrostat function
Start
End
Continuous hygrostat function
Max. speed
Continuous hygrostat function
Max. stage
Continuous hygrostat function
Max. fresh air rate
Automatic start for
hygrostat function
Set humidity level (relative)
Set humidity level (absolute)
Max. r.h., vent. air
Minimum humidifier control
Minimum humidifier runtime
Humidifier run-on time, drying
Enable below outside
temperature
Enable below outside
temperature
Delay, temperature priority
control
Humidifier start delay
Reference temp. for set
humidity level
* with adiabatic humidifier
** with isothermal humidifier
To determine the absolute humidity, use the h,x diagram.
As an example, the absolute humidity (9.4 g/kg) at a temperature of 24 °C and a
relative humidity of 50 % has been calculated.
Setting range
0 - 100 %
1 - 3
0 - 100 %
0 - 100 % r.h.
0 - 100 % r.h.
20 - 100 %
Stage 1-3
0 - 100 %
Yes/No
10 - 95 % r.h.
2 - 30 g/kg
50 - 100 % r.h.
0 - 100 %
0 - 99 min
0 - 99 min
Yes/No
0 - 40 °C
0 - 60 min
0 - 99 min
Actual temperature /
Actual temperature
set temperature
Factory setting
100 %
3
80 %
60 % r.h.
80 % r.h.
100 %
Stage 3
100 %
No
50 % r.h.
8 g/kg
90 % r.h.
35 %
0 min.* / 10 min.**
10 min.* / 2 min.**
No
15 °C
5 min.
5 min.* / 2 min.**