10. Operating level 2
Quick heating
Prerequisite:
− Extract air temperature sensor or room temperature sensor installed
− Damper system for quick heat-up installed
The quick heat-up function can be enabled in the "standard settings".
During system start-up and in control mode, the ACTUAL room/extract air
temperature and the SET room/extract air temperature are continuously
compared. If the actual temperature is below the set temperature by
an adjustable value (e.g. 5 K), the quick heat-up function is enabled.
This means recirculating air operation with the set maximum supply air
temperature.
Once the ACTUAL room/extract air temperature has reached the SET room/
extract air temperature (incl. adjustable offset), the unit changes back into
control mode.
If the SET room/extract air temperature (incl. offset) is not achieved, the
unit switches back into control mode after an adjustable max. runtime (e.g.
60 min).
If the quick heat-up function is enabled, this is shown on the default screen
as a special operating mode.
Parameter
Start delay for fan
Start time for recirc. mode
Min. proportion fresh air with
modulating reduction
Modulating reduction, min. proportion
fresh air with outside temp.
standard fresh air proportion
Reduced fresh air proportion
Energy saving
- heating
- cooling
Delta of set/actual room temperature
Offset, set temperature
Offset, ventilation air*
Substit. set room temperature**
Max. runtime
* the set percentage applies to the set supply air value
(e.g. set value = 2000 m³/h + 10 % offset -> quick heat-up set value = 2200 m³/h)
** is effective with selected supply air temperature control
Setting range
Factory setting
0 - 180 s
120 s
0 - 180 min
0 min
0 - 100 %
10 %
-10 - 30 °C
-10 - 30 °C
-10 °C
0 - 30 K
10 K
0 - 30 K
10 K
2 - 10 K
-1 - 5 K
0-100 %
15 - 35 °C
22 °C
10 - 90 min
60 min
3062878_201707
0 °C
5 K
0 K
0 %

Hide quick links: