10.2.12 Extension time

Extension time
Extension time
Esc BACK
SELECTION

10.2.13 Peak ventilation

Peak ventilation
Runtime
Esc BACK
SELECTION
42
10. Operating level 2
Standard mask
N-01
The extension of utilisation time can be activated either in the standard
settings or via the BMK-F remote control. When the extension of utilisation
time is activated, the system runs for at least the time set. The extension
30 min
time can be selected at the remote control, if the extension of utilisation time
is activated via the BMK-F remote control. If the extension of utilisation time
is activated whilst the system is shut down, it will start for the selected time.
DISPLAY
The set values last active will become active again.
Setback mode makes the stop times in the time program overlap subject to
outside temperature. It can be enabled or disabled.
This function counteracts any formation of ice on the external units, since
moisture rising through the duct is permanently removed from the appliance.
This function will be active when it is enabled and when the outside
temperature lies below the set limit.
During this time, the fans will run at the set minimum speed and the fresh air
damper will be switched to minimum fresh air proportion.
Special operating modes that increase the speed or fresh air proportion (for
example air quality regulation etc.) remain disabled during setback mode.
Parameter
Extension time
Enable setback mode
Outside temp limit for setback mode
Standard mask
ventilation
SL-01
The peak ventilation can be activated either in the standard settings or via the
BMK-F remote control. When peak ventilation is active, the fresh air proportion,
20 min
the fan stage, the fan speed, the pressure or the air volume are increased to a
programmed value. The "Runtime" parameter will only be valid if the activation took
place at the programming module. The time can be selected at the remote control, if
the activation was made at the BMK-F remote control.
DISPLAY
Parameter
Runtime
Fresh air
Fan stage
Fan speed
Pressure
Flow rate
Main menu
Heating contractor
Esc
Main menu
Esc
0 - 120,000 m³/h
Extension time
Setting range
Factory setting
5 - 720 min
30 min
Yes/No
-20 - 50 °C
Heating contractor
Setting range
Factory setting
5 - 300 min
20 min
0 - 100 %
100 %
Stage 1 - 3
Stage 3
0 - 100 %
100 %
0 - 1000 Pa
250 Pa
1000 m³/h
3062878_201707
No
0 °C
Peak