Alarm messages
Frost thermostat responded
(AL13)
Frost prot. temp. vent. air
below set value (AL14)
Temperature limiter,
electric heater bank (AL15)
Safety temperature limiter
elec. htr bank (AL16)
Fault, pump, cold water
bank (AL17)
Central fault ext
refrigeration unit (AL18)
Fire alarm system
responded (AL19)
Vent. temp sensor faulty or
not connected (AL20)
Vent. air hum. sensor faulty
or not connected (AL21)
Room temp sensor faulty or
not connected (AL22)
Indoor air humidity sensor
faulty or not connected
(AL23)
Extr. air temp sensor faulty
or not connected (AL24)
Extr. air hum. sensor faulty
or not connected (AL25)
3062878_201707
14. Fault messages
Effects
Cause
Fans are switched
Temperature captured
off; outdoor air
at the thermostat below
damper is closed;
limit
heating circuit pump
starts; heating circuit
mixer is opened; heat
source receives a
demand
Fans are switched
Supply air temperature
off; outdoor air
too low
damper is closed;
heating circuit pump
starts; heating circuit
mixer is opened; heat
source receives a
demand. With electric
heater bank: System
off
The system shuts
Electric heater bank
down after a delay
temperature too high
The system shuts
Electric heater bank
down after a delay
temperature too high
Pump off, cooling
An overload relay of an
valve closed, demand
external cooling circuit
chiller off
pump has responded
Chiller is switched off
Cooling unit / direct
evaporator has
recognised a fault;
cooling unit / direct
evaporator faulty
Subject to parameter
Smoke detector has
settings, either
responded
system OFF, only
message or smoke
extraction
The system shuts
Sensor or lead faulty
down
Humidifier shuts
Sensor or lead faulty
down; system
continues to operate
The system shuts
Sensor or lead faulty
down
Humidifier shuts
Sensor or lead faulty
down; system
continues to operate
If an extract air /
Sensor or lead faulty
supply air cascade
is installed:
System OFF
otherwise
message only
Humidifier shuts
Sensor or lead faulty
down; system
continues to operate
Remedy
Check heating medium;
check heating circuit pump;
check frost stat, acknowledge
fault message
Check heating medium;
check heating circuit pump;
check parameters, acknowledge
fault message
Check heater bank;
acknowledge fault message
Check heater bank;
acknowledge fault message
Reset overload relay; check
power drawn by the pump;
acknowledge fault message
Check cooling unit / direct
evaporator; acknowledge fault
message
Acknowledge fault message
Check sensor and lead,
acknowledge fault message
Check sensor and lead,
acknowledge fault message
Check sensor and lead,
acknowledge fault message
Check sensor and lead,
acknowledge fault message
Check sensor and lead,
acknowledge fault message
Check sensor and lead,
acknowledge fault message