Flow Rate For External Demand; Automatic Start Via External Demand; Set Humidity Level; 7-Day Program Operating Mode - Wolf WRS-K Installation And Operating Instructions Manual

Regulatory system
Table of Contents

Advertisement

Flow rate for external demand

STANDARD SETTING
Flow rate, vent. air for
external demand
Stage 3:
2000 m³/h
Stage 2:
1500 m³/h
Stage 1:
1000 m³/h
Esc BACK
SELECTION
Automatic start via external
demand
STANDARD SETTING

Automatic start via external demand

(YES)
Esc BACK
SELECTION

Set humidity level

STANDARD SETTING
Set value, vent air rh
50 % r.h.
Esc BACK
SELECTION

7-day program operating mode

STANDARD SETTING
7-day program active
Esc BACK
SELECTION
Enabling / disabling
backup mode, heating
STANDARD SETTING
Backup mode,
heating active
(YES)
Esc BACK
SELECTION
Enabling / disabling
backup mode, cooling
STANDARD SETTING
Backup mode,
cooling active
(YES)
Esc BACK
SELECTION
18
9. Operating level 1
Pressing
highlights the flow rate that can then be changed with
Finally confirm the selected value with
GE-14
For ventilation systems, the flow rates for supply and extract air for external demand
are changed separately.
DISPLAY
Pressing
enables the functionality of the external stage demand to be defined. If
this parameter is set to "Yes", the system will start even if a demand falls outside the
period defined by the 7-day program.
GE-30
If this parameter is set to "No", the stage demand only becomes active during the
operating hours.
DISPLAY
Pressing
Finally confirm the selected value with
GE-16
DISPLAY
Pressing the
with the
GE-18
Please note The 7-day program is activated at the factory.
DISPLAY
Pressing
to be disabled. For adjustment options and changes, see chapter Backup mode.
(Prerequisite: room temperature sensor available)
GE-19
DISPLAY
Pressing
to be disabled. For adjustment options and changes, see chapter Backup mode.
(Prerequisite: room temperature sensor available)
GE-20
DISPLAY
highlights the set humidity level that can then be changed with
button highlights the operating mode, which can then be adjusted
buttons.
enables the backup mode, heating to be enabled or, by pressing again,
enables the backup mode, cooling to be enabled or, by pressing again,
.
.
3062878_201707
.
.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

KlmBmkBmf

Table of Contents