10
TROUBLESHOOTING
Error code
0BBDh
0BBEh
0BBFh
0BC0h
0BC1h
0BC2h
0BC3h
0BC4h
0BC5h
0BC6h
0BC7h
0BC8h
0C00h
to
0C56h
0C80h
0C81h
Table 10.3 Error codes for the MES interface module
Error name
Execution error (Program
Failed to log on to the application
execution function)
server.
The application server has failed to
acquire user-identifying information.
The profile of the specified user was
not found in the application server.
The application server has failed to
add a privilege for program execution.
The application server has failed to
Execution error (Program
load the user profile.
execution function)
The application server has failed to
add an access right for screen display.
The application server has failed to
start a program.
Failed to retrieve a loaded user file.
The application server has failed to
terminate exclusion control.
Function incompatible with DB
DB connection service
Connection Service version of
version error
connection target is used.
Stored procedure
The stored procedure execution has
execution error
been failed.
System error
CF card check error
Failed to access the CompactFlash
(event log writing)
card during event log output.
Remaining capacity of the
CF card full error (event
CompactFlash card is not sufficient for
log writing)
writing the event log.
Description
10.2 Error Code List
10.2.1 Error codes for the MES interface module
(From the previous page)
Action
• Check if the program specified with
the program execution function is
executable with the specified
account.
• After creating an account used for
the program execution function, be
sure to log in once at least.
• A user with an empty password
cannot be specified.
Set a password for the specified
user.
• Check if the program specified with
the program execution function is
executable with the specified
account.
• Check if the program specified with
the program execution function is
executable with the specified
account.
• Install the latest version of DB
Connection Service to a server
computer of the connection target.
• Check if the settings of the stored
procedures, return values, and
arguments are correct.
• Check if the data type between the
argument and the input argument
and input/output argument of the
stored procedure to be passed are
the same.
• Check that reserved terms of the
database are not set for the stored
procedure names.
• Please consult your local Mitsubishi
representative.
• Check if the CompactFlash card is
damaged.
• Turn the power OFF and ON, or
reset the programmable controller
CPU.
• Check the capacity of the
CompactFlash card.