Smoothing
The individual measured values are smoothed by filtering. The smoothing can be set in 4
levels and channel-selective in STEP 7 (TIA Portal).
Smoothing time = Smoothing (k) x configured integration time
The following figure shows the time it takes for the smoothed analog value to reach
approximately 100 % depending on the set smoothing. This is valid for all signal changes at
the analog input.
None (smoothing = 1 x integration time)
Weak (smoothing = 4 x integration time) *
Medium (smoothing = 16 x integration time) *
Strong (smoothing = 32 x integration time) *
* The smoothing time can increase by 1 x integration time.
Figure C-5
Smoothing time depending on the set smoothing level
The following table shows the time it takes for the smoothed analog value to reach
approximately 100 % depending on the set smoothing and the set interference frequency
suppression.
Table C- 2
Smoothing time depending on the set smoothing level and interference frequency suppression
Selection of the smoothing
(mean value generation from scan values)
None
Weak
Medium
Strong
CPU 1512C-1 PN (6ES7512-1CK01-0AB0)
Manual, 12/2017, A5E40898741-AA
Interference frequency suppression/smoothing time
400 Hz
60 Hz
2.5 ms
16.6 ms
10 ms
66.4 ms
40 ms
265.6 ms
80 ms
531.2 ms
Analog value processing
C.1 Conversion method
50 Hz
10 Hz
20 ms
100 ms
80 ms
400 ms
320 ms
1600 ms
640 ms
3200 ms