Siemens CM 1542-5 Operating Instructions Manual

Siemens CM 1542-5 Operating Instructions Manual

Simatic net, profibus
Hide thumbs Also See for CM 1542-5:

Advertisement

SIMATIC NET
S7-1500 - PROFIBUS
CM 1542-5
Operating Instructions
11/2018
C79000-G8976-C290-04
___________________
Preface
___________________
Guide to the documentation
___________________
Product overview, functions
___________________
Installation, connecting up,
commissioning, operation
___________________
Configuration, programming
___________________
Diagnostics and upkeep
___________________
Technical specifications
___________________
Approvals
1
2
3
4
5
6
7

Advertisement

Table of Contents
loading

Summary of Contents for Siemens CM 1542-5

  • Page 1 ___________________ Preface ___________________ Guide to the documentation ___________________ SIMATIC NET Product overview, functions ___________________ Installation, connecting up, commissioning, operation S7-1500 - PROFIBUS CM 1542-5 ___________________ Configuration, programming ___________________ Diagnostics and upkeep Operating Instructions ___________________ Technical specifications ___________________ Approvals 11/2018 C79000-G8976-C290-04...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Preface

    ● New ATEX/IECEx approval Replaced edition Edition 10/2016 Current manual edition on the Internet You will also find the current version of this manual on the Internet pages of Siemens Industry Online Support: Link: (https://support.industry.siemens.com/cs/ww/en/ps/15671/man) Sources of information and other documentation See section Guide to the documentation (Page 9).
  • Page 4: Operating Instructions, 11/2018, C79000-G8976-C290

    You will find license conditions in the following document on the supplied data medium: ● OSS_CM15425_86.pdf Firmware The firmware is signed and encrypted. This ensures that only firmware created by Siemens can be downloaded to the device. Security information Siemens provides products and solutions with industrial security functions that support the secure operation of plants, systems, machines and networks.
  • Page 5 Siemens contact. Keep to the local regulations. You will find information on returning the product on the Internet pages of Siemens Industry Online Support: Link: (https://support.industry.siemens.com/cs/ww/en/view/109479891)
  • Page 6 Preface CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 7: Table Of Contents

    Notes on use in hazardous areas according to UL HazLoc ........... 22 3.1.4 Notes on use in hazardous areas according to FM ..............23 Installing and commissioning the CM 1542-5 ................. 23 Pin assignment PROFIBUS ....................24 Mode of the CPU - effect on the CM ..................25 Configuration, programming ........................
  • Page 8 Device-specific diagnostics in DP-V1 ..................39 DP diagnostics frames when the CPU is in STOP ..............42 Replacing a module without a programming device .............. 42 Technical specifications ........................43 Approvals ............................. 45 Index ..............................51 CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 9: Guide To The Documentation

    Overview of the documentation on communication with S7-1500 The following table lists additional documents, which supplement this description of CM 1542-5 and are available in the Internet. Table 1- 1 Documentation for the CM 1542-5 Topic...
  • Page 10 Version History / current downloads for the SIMATIC NET S7-CPs/CMs The "Version History/Current Downloads for SIMATIC NET S7 CPs (PROFIBUS)" provides information on all CPs available up to now for SIMATIC S7 (PROFIBUS). You will find the document on the Internet: Link: (https://support.industry.siemens.com/cs/ww/en/view/67225941) CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 11: Product Overview, Functions

    This description contains information on the following product: CM 1542-5 Article number 6GK7 542-5DX00-0XE0 Hardware product version 1 Firmware version V2.0.15 Communications module CM 1542-5 for connection of S7-1500 to PROFIBUS DP View of the module ① LEDs ② Type plate ③...
  • Page 12: Application

    – DP master mode for DP slaves according to PROFIBUS DP-V0 and DP-V1 – DP master mode for Siemens DP slaves – Direct data exchange (DP slave to DP slave) As a DP master, the CM 1542-5 is capable of enabling direct data exchange for its assigned DP slaves. – SYNC/FREEZE The outputs or inputs can be synchronized by the user program using system function DPSYNC_FR.
  • Page 13: Further Functions

    Data records from devices that are not connected directly to PROFIBUS and therefore have no direct access to the DP slaves are forwarded to the DP slaves by the CM. The services of the CM 1542-5 listed above can be used independently at the same time. Note...
  • Page 14: Configuration Limits And Performance Data

    2.4 Configuration limits and performance data Time-of-day synchronization - time master or time slave The CM 1542-5 can be enabled for time-of-day synchronization. As an alternative, the CM can be configured as time master or time slave on PROFIBUS. ● Time master: The CM is synchronized using the time of day in the S7-1500 station and outputs the time of day on PROFIBUS.
  • Page 15: Transmission Speeds Supported

    * When using DP slaves with extensive configuration data e.g. SINAMICS devices, the number of DP slaves that can be operated on the CM sinks. Diagnostics requests As a DP master (class 1), the CM 1542-5 supports diagnostics requests of a DP master (class 2). CM 1542-5...
  • Page 16: Characteristic Data Of Fdl Communication

    For this reason, lower values than specified here can result. You will find detailed information on the topic of connection resources in the "Communication" function manual, see Communication (http://support.automation.siemens.com/WW/view/en/59192925). CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 17: Characteristics Of S7 Communication

    Performance data / operation Measured values of transfer or reaction times Measured values of transfer and reaction times in Ethernet, PROFIBUS and PROFINET networks for a series of configurations can be found on the Internet: Link: (https://support.industry.siemens.com/cs/ww/en/view/25209605) CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 18: Requirements For Use

    STEP 7 Professional V14 The full functionality of the CP 1542-5 (6GK7 542-5DX00-0XE0) can be programmed. Use of FDL For programming and using FDL, the following minimum firmware versions are required. ● CM: V2.0 ● CPU: V2.0 CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 19: Leds

    Figure 2-2 LED display of the CM 1542-5 (without front cover) Meaning of the LED displays The CM 1542-5 has 3 LEDs to display the current operating status and the diagnostics status and these have the following meanings: (one-color LED: green) •...
  • Page 20: Profibus Interface

    You also have the option of connecting to optical PROFIBUS networks via an Optical Bus Terminal OBT or an Optical Link Module OLM. You will find the pin assignment of the D-sub socket in section Pin assignment PROFIBUS (Page 24). CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 21: Installation, Connecting Up, Commissioning, Operation

    Zone 2, the device must be installed in a cabinet or a suitable enclosure. WARNING DIN rail In the ATEX and IECEx area of application only the Siemens DIN rail 6ES5 710-8MA11 may be used to mount the modules. CM 1542-5...
  • Page 22: Notes On Use In Hazardous Areas According To Atex / Iecex

    This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or non- hazardous locations only. This equipment is suitable for use in Class I, Zone 2, Group IIC or non-hazardous locations only. CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 23: Notes On Use In Hazardous Areas According To Fm

    Installation, connecting up, commissioning, operation 3.2 Installing and commissioning the CM 1542-5 3.1.4 Notes on use in hazardous areas according to FM WARNING EXPLOSION HAZARD You may only connect or disconnect cables carrying electricity when the power supply is switched off or when the device is in an area without inflammable gas concentrations.
  • Page 24: Pin Assignment Profibus

    RS485 interface. Table 3- 1 Terminal assignment PROFIBUS interface View Signal name Designation RxD/TxD-P Data line A Request To Send M5V2 Data reference potential (from station) P5V2 Supply plus (from station) RxD/TxD-N Data line B CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 25: Mode Of The Cpu - Effect On The Cm

    – The configuration and diagnostics of the CM Relevant system connections for configuration, diagnostics and PG channel routing still exist. – Data record routing – S7 routing function – Time-of-day synchronization – Configured connections remain established. CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 26 Installation, connecting up, commissioning, operation 3.4 Mode of the CPU - effect on the CM CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 27: Configuration, Programming

    Reading the process image partition of a DP standard slave SETIO_PART Transferring the process image partition of a DP standard slave D_ACT_DP Disable / enable DP slaves DPRD_DAT Reading consistent data of a DP standard slave (user data) CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 28: Program Blocks For Fdl

    STEP 7. The end point of an FDL connection is an S7-1500 CPU with communications module CM 1542-5. For the required firmware versions of the modules, see section Programming (Page 18).
  • Page 29 Connections are established using the program block TCON. Note that a separate program block TCON must be called for each connection. A separate connection must be established for each communications partner even if identical blocks of data are being sent. CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 30 Configured connection with an unspecified partner – Unspecified Layer 2 connection Programmed FDL-Verbindung with an unspecified partner with free layer 2 access – Broadcast connection Connection to all connected partners – Multicast connection Connection to several defined partners CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 31 – Unspecified 6. Select the following interfaces under Interfaces: – Local: PROFIBUS interface of CM 1542-5 – Specified partner: PROFIBUS interface of CM 1542-5 7. Select the setting <new> under Connection data. This creates a new connection between the two partners.
  • Page 32 5. Interconnect the CONNECT parameter of the TCON instruction with the previously created variable "FDL_Connection" of the data type TCON_FDL. In the example below, the CONNECT parameter of the TCON instruction is interconnected with the tag "FDL_Connection" (data type TCON_FDL). CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 33 ● RemoteSAP = specified, RemotePBAddress = 255 If you program a specific value for RemoteSAP and assign the value 255 for RemotePBAddress, data transfer from every partner with the specified address will be accepted via this connection. CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 34 Configuration, programming 4.3 Program blocks for FDL CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 35: Diagnostics And Upkeep

    The DP diagnostics of the CM is described below. The evaluation of diagnostics data records requested by the DP master and the diagnostics interrupts or diagnostics alarms of the DP slaves is handled in the user program of the DP master station. CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 36: Dp Slave Diagnostics

    The diagnostics data is transferred as a diagnostics interrupt. Diagnostics interrupts must be acknowledged by the DP master. Supported diagnostics functions The CM 1542-5 supports the following blocks of DP diagnostics: ● Standard diagnostics (6 bytes) ● Identifier-related diagnostics (2 to 17 bytes), depending on the number of configured transfer areas ●...
  • Page 37: Standard Diagnostics

    Bit =0: There may be status information in the slave-specific diagnostics • area. The status information can be evaluated in the user program of the master. CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 38 Structure of station status byte 3 Bit no. Name Explanation Ext_Data_Overflow If this bit is set, there is more diagnostics information available than indicated in the diagnostics data. This data cannot be displayed. 6...0 Reserved - reserved - CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 39: Device-Specific Diagnostics In Dp-V1

    Structure of byte 1 of the device-specific diagnostics (variant "interrupt type") Bit no. Meaning Value Meaning Interrupt 6...0 Alarm_Type - reserved - Diagnostics interrupt Hardware interrupt Pull interrupt Plug interrupt Status interrupt Update interrupt 7...31 - reserved - CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 40 Interrupt disappears, slot OK The slot generates the interrupt and indicates that it has no further errors. Interrupt disappears, slot still disrupted The slot generates an interrupt and indicates that it has further errors. CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 41 Table 5- 10 Meaning of the values of the status bits Value Meaning Data valid Data invalid - error (for example short-circuit) Data invalid - wrong module Data invalid - no module plugged in CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 42: Dp Diagnostics Frames When The Cpu Is In Stop

    General procedure The configuration data of the CM is stored on the CPU. This means that this module can be replaced by a module of the same type (identical article number) without using a PG. CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 43: Technical Specifications

    Note the information in the System description of SIMATIC S7-1500 (Page 9). In addition to the information in the system description, the following technical specifications apply to the module. Technical specifications - CM 1542-5 Product name CM 1542-5 Article number...
  • Page 44 Technical specifications CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 45: Approvals

    The approvals for shipbuilding are an exception to this. Certificates for shipbuilding and national approvals The device certificates for shipbuilding and special national approvals can be found in Siemens Industry Online Support on the Internet: Link: (https://support.industry.siemens.com/cs/ww/en/ps/15671/cert) EC declaration of conformity...
  • Page 46 Zone 2 Hazardous Area" that you will find on the Internet at the following address: Link: (https://support.industry.siemens.com/cs/ww/en/view/78381013) ATEX The product meets the requirements of the EC directive:2014/34/EC "Equipment and Protective Devices for Use in Potentially Explosive Atmospheres". CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 47 Electromagnetic compatibility (EMC) - Part 6-2: Generic standards - Immunity for industrial environments RoHS The product meets the requirements of the EC directive 2011/65/EU on the restriction of the use of certain hazardous substances in electrical and electronic equipment. CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 48 For devices with C-PLUG memory: The C-PLUG memory module may only be inserted or removed when the power is off. CSA Certification Mark Canadian Standard Association (CSA) nach Standard C 22.2 No. 142: ● Certification Record 063533–C-000 CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 49 SIMATIC NET products are regularly submitted to the relevant authorities and approval centers for approvals relating to specific markets and applications. If you require a list of the current approvals for individual devices, consult your Siemens contact or check the Internet pages of Siemens Industry Online Support: Link: (https://support.industry.siemens.com/cs/ww/en/ps/15671/cert)
  • Page 50 Approvals CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 51: Index

    Slave mode, 25 Operating mode of the CPU, 25 DP slaves OUC (Open User Communication), 28 Quantity, 15 PG functions, 17 EMC - electromagnetic compatibility, 45 PG/OP communication, 12 PROFIBUS DP-V0 and DPV1 standard, 12 CM 1542-5 Operating Instructions, 11/2018, C79000-G8976-C290-04...
  • Page 52 RS-485 interface, 24 RS485 socket, 24 S7 communication, 12 S7 connections, 12, 17 S7 routing function, 25 Safety notices, 21 Siemens DP slave, 12 SIMATIC NET glossary, 5 SIMATIC NET Manual Collection, 10 Startup parameters DP, 16 STEP 7, 3 SYNC/FREEZE, 12...

This manual is also suitable for:

S7-1500

Table of Contents