Article number
Input ranges (rated values), currents
0 to 20 mA
Input resistance (0 to 20 mA)
-20 mA to +20 mA
Input resistance (-20 mA to +20 mA)
4 mA to 20 mA
Input resistance (4 mA to 20 mA)
Input ranges (rated values), resistance thermome-
ter
Ni 100
Input resistance (Ni 100)
Pt 100
Input resistance (Pt 100)
Input ranges (rated values), resistors
0 to 150 ohms
Input resistance (0 to 150 ohms)
0 to 300 ohms
Input resistance (0 to 300 ohms)
0 to 600 ohms
Input resistance (0 to 600 ohms)
Cable length
shielded, max.
Analog outputs
integrated channels (AO)
Voltage output, short-circuit protection
Cycle time (all channels), min.
Output ranges, voltage
0 to 10 V
1 V to 5 V
-10 V to +10 V
CPU 1512C-1 PN (6ES7512-1CK01-0AB0)
Manual, 12/2017, A5E40898741-AA
6ES7512-1CK01-0AB0
Yes; Physical measuring range: ± 20 mA
50 Ω; Plus approx. 55 ohm for overvoltage pro-
tection by PTC
Yes
50 Ω; Plus approx. 55 ohm for overvoltage pro-
tection by PTC
Yes; Physical measuring range: ± 20 mA
50 Ω; Plus approx. 55 ohm for overvoltage pro-
tection by PTC
Yes; Standard/climate
10 MΩ
Yes; Standard/climate
10 MΩ
Yes; Physical measuring range: 0 ... 600 ohms
10 MΩ
Yes; Physical measuring range: 0 ... 600 ohms
10 MΩ
Yes
10 MΩ
800 m; for U/I, 200 m for R/RTD
2
Yes
1 ms; Dependent on the parameterized interfer-
ence frequency suppression; for details, see
conversion procedure in manual
Yes
Yes
Yes
Technical specifications