Siemens Simatic S7-1500 CPU 1512C-1 PN User Manual page 126

Hide thumbs Also See for Simatic S7-1500 CPU 1512C-1 PN:
Table of Contents

Advertisement

Parameters/address space
5.7 Parameters of the digital on-board I/O
Configurable parameters and default settings for inputs
Table 5- 10
Configurable parameters for inputs
Parameters
1)
Diagnostics
No
supply voltage L+
Input delay
Hardware interrupt
Rising edge
Falling edge
All parameters can be set channel-selective
1)
Configurable parameters and default settings for outputs
Table 5- 11
Configurable parameters for outputs
Parameters
1)
Diagnostics
Missing
supply voltage L+
Reaction to CPU STOP
When the digital output is controlled by a
technology channel (HSC, PTO or PWM),
this parameter is not effective. In this case
the technology channel specifies the reac-
tion of the digital output to CPU STOP.
All parameters can be set channel-selective
1)
126
Value range
Yes/No
None, 0.05 ms, 0.1 ms,
0.4 ms, 1.6 ms, 3.2 ms,
12.8 ms, 20 ms
Yes/No
Yes/No
Value range
Yes/No
Turn off
Keep last value
Output substitute value 1
Default
Reconfiguration in RUN
No
Yes
3.2 ms
Yes
No
Yes
No
Yes
Default
Reconfiguration in RUN
No
Yes
Turn off
Yes
CPU 1512C-1 PN (6ES7512-1CK01-0AB0)
Manual, 12/2017, A5E40898741-AA

Advertisement