Technical specifications
Article number
Data areas and their retentivity
Retentive data area (incl. timers, counters,
flags), max.
Extended retentive data area (incl. timers,
counters, flags), max.
Flag
Number, max.
•
Number of clock memories
•
Data blocks
Retentivity adjustable
•
Retentivity preset
•
Local data
per priority class, max.
•
Address area
Number of IO modules
I/O address area
Inputs
•
Outputs
•
per integrated IO subsystem
–
Inputs (volume)
–
Outputs (volume)
per CM/CP
–
Inputs (volume)
–
Outputs (volume)
Subprocess images
Number of subprocess images, max.
•
Hardware configuration
Number of distributed IO systems
Number of DP masters
Via CM
•
Number of IO Controllers
integrated
•
Via CM
•
144
6ES7512-1CK01-0AB0
128 kbyte; In total; available retentive memory for
bit memories, timers, counters, DBs, and tech-
nology data (axes): 88 KB
1 Mbyte; When using PS 60W 24/48/60V DC HF
16 kbyte
8; 8 clock memory bits, grouped into one clock
memory byte
Yes
No
64 kbyte; max. 16 KB per block
2 048; max. number of modules / submodules
32 kbyte; All inputs are in the process image
32 kbyte; All outputs are in the process image
8 kbyte
8 kbyte
8 kbyte
8 kbyte
32
32; A distributed I/O system is characterized not
only by the integration of distributed I/O via
PROFINET or PROFIBUS communication mod-
ules, but also by the connection of I/O via AS-i
master modules or links (e.g. IE/PB-Link)
6; A maximum of 6 CMs/CPs (PROFIBUS,
PROFINET, Ethernet) can be inserted in total
1
6; A maximum of 6 CMs/CPs (PROFIBUS,
PROFINET, Ethernet) can be inserted in total
CPU 1512C-1 PN (6ES7512-1CK01-0AB0)
Manual, 12/2017, A5E40898741-AA