Technical specifications
Article number
Crosstalk between the outputs, max.
Repeat accuracy in steady state at 25 °C (rela-
tive to output range), (+/-)
Operational error limit in overall temperature
range
Voltage, relative to input range, (+/-)
•
Current, relative to input range, (+/-)
•
Resistance, relative to input range, (+/-)
•
Resistance thermometer, relative to input
•
range, (+/-)
Voltage, relative to output range, (+/-)
•
Current, relative to output range, (+/-)
•
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)
•
Current, relative to input range, (+/-)
•
Resistance, relative to input range, (+/-)
•
Resistance thermometer, relative to input
•
range, (+/-)
Voltage, relative to output range, (+/-)
•
Current, relative to output range, (+/-)
•
Interference voltage suppression for f = n x (f1 +/-
1 %), f1 = interference frequency
Series mode interference (peak value of
•
interference < rated value of input range),
min.
Common mode voltage, max.
•
Common mode interference, min.
•
Interfaces
Number of PROFINET interfaces
1. Interface
Interface types
Number of ports
•
integrated switch
•
RJ 45 (Ethernet)
•
152
6ES7512-1CK01-0AB0
-80 dB
0.05 %
0.3 %
0.3 %
0.3 %
Pt100 Standard: ±2 K, Pt100 Climate: ±1 K,
Ni100 Standard: ±1.2 K, Ni100 Climate: ±1 K
0.3 %
0.3 %
0.2 %
0.2 %
0.2 %
Pt100 Standard: ±1 K, Pt100 Climate: ±0.5 K,
Ni100 Standard: ±0.6 K, Ni100 Climate: ±0.5 K
0.2 %
0.2 %
30 dB
10 V
60 dB; at 400 Hz: 50 dB
1
2
Yes
Yes; X1
CPU 1512C-1 PN (6ES7512-1CK01-0AB0)
Manual, 12/2017, A5E40898741-AA