Siemens Simatic S7-1500 CPU 1512C-1 PN User Manual page 123

Hide thumbs Also See for Simatic S7-1500 CPU 1512C-1 PN:
Table of Contents

Advertisement

Table 5- 6
Configurable "Measuring" parameters
Parameters
Measuring
Measurement type
Measuring range
Temperature coefficient
Temperature unit
Interference frequency suppression
Smoothing
All parameters can be set channel-selective
1)
Kelvin (K) is only possible for the "Standard range" measuring range and not for the "Climatic range" measuring range
2)
The interference frequency suppression must have the same value for all active input channels. This value can only be
3)
changed through reconfiguration in RUN with single channel parameter assignment (data records 0 to 4) if all other in-
put channels are disabled.
Table 5- 7
Configurable "Hardware interrupt" parameters
Parameters
Hardware interrupts
Hardware interrupt low limit 1
Hardware interrupt high limit 1
Hardware interrupt low limit 2
Hardware interrupt high limit 2
All parameters can be set channel-selective
1)
You can find an overview of the limits for the hardware interrupts in the section Structure of a
data record for input channels of the analog on-board I/O (Page 166).
CPU 1512C-1 PN (6ES7512-1CK01-0AB0)
Manual, 12/2017, A5E40898741-AA
1)
See section Measurement
types and measuring ranges
of the analog on-board I/O
(Page 120)
Pt: 0.003851
Pt: 0.003916
Pt: 0.003902
Pt: 0.003920
Ni: 0.006180
Ni: 0.006720
Kelvin (K)
Fahrenheit (°F)
Celsius (°C)
400 Hz
60 Hz
50 Hz
10 Hz
None/weak/medium/strong
1)
Yes/No
Yes/No
Yes/No
Yes/No
5.6 Parameters of the analog on-board I/O
Value range
Voltage
(channels 0 to 3)
Resistance
(channel 4)
±10 V
(channels 0 to 3)
600 Ω
(channel 4)
0.003851
°C
2)
50 Hz
None
Value range
No
No
No
No
Parameters/address space
Default
Reconfiguration in RUN
Yes
Yes
Yes
Yes
Yes
3)
Yes
Default
Reconfiguration in RUN
Yes
Yes
Yes
Yes
123