Advertisement

Code
S:39 * Transducer temperature sensor failure..
S:40
Transducer temperature too high.
S:41
Transducer temperature too low.
S:42
Factory calibration for the transducer
temperature sensor has been lost.
S:43 * Factory calibration for the radar receiver has
been lost.
S:44 * Factory calibration for the echo slope has
been lost.
S:45 * No valid boot program detected: firmware
corrupt.
S:48 * User configuration is invalid. One or more of
parameters: Span, Volume breakpoints, and/or
Auto False-Echo Suppression, are set to
invalid values.
S:49 * EEPROM corrupt.
S:50 * EEPROM corrupt.
Page 84
SITRANS Probe LU (HART) – OPERATING INSTRUCTIONS
Meaning
Corrective Action (cont' d )
Reset power. If fault persists,
contact your local Siemens
representative: repair required.
Relocate device and/or lower
process temperature enough to
cool device. Inspect for heat-
related damage and contact your
local Siemens representative if
repair is required.
Relocate device and/or raise
process temperature enough to
warm device. Inspect for damage
and contact your local Siemens
representative if repair is required.
Repair required: contact your local
Siemens representative.
Repair required: contact your local
Siemens representative.
Repair required: contact your local
Siemens representative.
Repair required: contact your local
Siemens representative.
Reconfigure the unit. Ensure Span
(P007) is not set to 0; check the
breakpoints (only required if P050 is
set to 9); do a P999 reset.
Repair required: contact your local
Siemens representative.
Repair required: contact your local
Siemens representative.