P005 Units
Specifies measurement units used for dimensional values.
Values
P006 Empty (process empty level)
Sets the distance from the transducer face to the process empty level, in units selected at
P005.
Range
(depends
on model
Values
Default
Enter the distance from the transducer face
to Empty (process empty level), using units
set in P005. Empty can be set to any
distance: not necessarily the bottom of the
vessel
Notes:
• Default setting is maximum range.
• P006 and P007 are interlinked: see note
attached to P007.
P007 Span (process full level)
Sets the range to be measured (referenced from Empty) in units selected at P005.
Range
(depends on model)
Values
Enter the distance between Empty (process empty level) and Span (process full level), in
units set in P005. Span can be set at any distance above Empty level.
A5E32337695
SITRANS Probe LU (HART) – OPERATING INSTRUCTIONS
1
*
meters
2
centimeters
3
millimeters
4
feet
5
inches
0.0000 to 6.10 m (20.01 ft)
or
0.0000 to 12.20 m (40.02 ft)
Max. range:
6.10 m (20.01 ft) or
12.20 m (40.02 ft)
0.0000 to 6.00 m (20 ft) or
0.0000 to 12 m (40 ft)
5.725 m (18.78 ft) or
Default
11.725 m (38.47 ft)
See note on next page for more details.
transducer
face
Span
100%
P007
P006
Empty
0%
1
Level Setup
Level
Page 33