If the value in this register is set to 1, the behavior during a field bus error is used.

4.4.25 0x1137 Data Format

If the value in this register is set to 0, data is transferred in Motorola format.
If the value in this register is set to 1, data is transferred in Intel format.
4.4.26 0x113C – 0x113F Save Module Parameters
Load default module parameters (0x113C – 0x113D) loads the default parameter set of all modules
(LOAD). This conforms to the Standard option in the web server.
Save module parameters (0x113E – 0x113F) stores the current image of all module parameters in
the network adapter (SAVE). Subsequent changes will not be considered unless they are saved again.
There is no need to enter parameters again after restarting the network adapter. This conforms to
the Yes option in the web server.
Inputs in both register in the Motorola format follow this scheme:
Letter of the alphabet
ASCII code decimal
ASCII hexadecimal
Input in register no.
Hexadecimal
Decimal
Using the Intel format the inputs follow "DAOL" and "EVAS":
Letter of the alphabet
ASCII code decimal
ASCII hexadecimal
Input in register no.
Hexadecimal
Decimal
The not editable parameter Restore module parameters in the web server will be set to Yes as soon as
the network adapter has sent saved parameters to the modules.

4.4.27 0x27FE Number of Entries in the Current Module List

This displays the number of modules that were connected when the network adapter was started.

4.4.28 0x27FF Number of Entries in the Reference Module List

This displays the number of modules that were entered into the reference list.
4.4.29 0x2800 – 0x287F Reference Module List
Each module identifier is made up of 4 bytes (2 registers). If a 1 is set in register 1132, the reference
module list must be identical to the current module list before the data exchange can begin.
4.4.30 0x2A00 – 0x2A7F Current Module List
Each module identifier is made up of 4 bytes (2 registers) (refer to the Overview of module IDs). The
modules that were connected when the network adapter was started are entered here. To simplify
configuration, the current module list can be copied into the reference module list.
4.4.31 0x2B00 – 0x2B7F Module offsets of process data
For each module there are two registers reserved to indicate the offset between the start address
within the packed pro- cess data and the address 0x0000: The first register indicates the bit-offset of
the outputs, the second one indicates the bit-offset of the inputs. Thus, it is possible to use these
GFK-2958E
Chapter 4 Detailed Descriptions of the Fieldbus Network Adapters
"LOAD"
L
O
A
076
079
065
4C
4F
41
0x113C
4C4F
19535
"DAOL"
D
A
O
068
065
079
44
41
4F
0x113C
4441
17473
RSTi-EP User Manual
D
S
068
083
44
53
0x113D
0x113E
4144
5341
16708
21313
L
E
076
069
4C
45
0x113D
0x113E
4F4C
4556
20300
17750
"SAVE"
A
V
E
065
086
069
41
56
45
0x113F
5645
22085
"EVAS"
V
A
S
086
065
083
56
41
53
0x113F
4153
16723
91