Rsti-Ep Status Messages - GE RSTi-EP User Manual

Standalone 1ghz programmable controller
Hide thumbs Also See for RSTi-EP:
Table of Contents

Advertisement

4.3.4 RSTi-EP Status Messages

In addition to the process input data a network adapter status word as well as module status bytes
are transfered to the SPS. Thus diagnostics and status messages can be read directly.
The network adapter status word describes the status of the RSTi-EP station including the following
information:
Bit
Name
Summarized module
0
diagnosis
1
Errorbit 1
2
Errorbit 2
3
Systembus error
4
Errorbit 4
5
Errorbit 5
I/O-Configuration
6
error
Master configuration
7
error
8
Errorbit 8
9
Errorbit 9
10
Force mode active
11
Errorbit 11
12
Errorbit 12
13
Voltage U
error
OUT
14
Voltage U
error
IN
15
Errorbit 15
GFK-2958E
Chapter 4 Detailed Descriptions of the Fieldbus Network Adapters
Network Adapter Status Bits EPXETC001
Description
Module diagnostic is present. A diagnosis is available for at least one module with
diagnostics functionality.
Reserve bit 1, currently not used
Reserve bit 2, currently not used
Error on the system bus. Communication with the connected modules is disrupted.
Reserve bit 4, currently not used
Reserve bit 5, currently not used
Deviation in the configuration. The module list has changed. The list of configured
modules (Configured Module Ident List 0xF030) differs from the module list detected by
the network adapter (Detected Module Ident List 0xF050).
Master configuration error. The list of configured modules (Configured Module Ident List
0xF030) differs significantly from the module list detected by the network adapter
(Detected Module Ident List 0xF050). No process data can be exchanged with the
modules. The station switches into PRE OPERATIONAL state.
Reserve bit 8, currently not used
Reserve bit 9, currently not used
Web server Force mode is active. Force mode was activated through the web server.
Process data cannot be exchanged between the EtherCAT master and forced channels.
Reserve bit 11, currently not used
Reserve bit 12, currently not used
Error in the supply voltage of outputs
Error in the supply voltage of system and inputs
Reserve bit 15, currently not used
RSTi-EP User Manual
73

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gfk-2958e

Table of Contents