Chapter 5 Detailed Descriptions of I/O Modules

5.12 Digital Output Module EP- 2814

Digital Output Module EP-2814
Connection Diagram EP-2814
The solid-state relay output module EP-2814 uses four semiconductor switches to control up to 4
discrete outputs, each with a maximum of 0.5 A at 255 V AC. The switching characteristics of the
semiconductor switch have it as being closed when the voltage crosses zero and open when the
current crosses zero. Each connector features a potential-free NO (Normally Open) contact.
For protection against extreme disturbance level, use surge protection terminals with varistor (refer
to the connection diagram).
GFK-2958E
RSTi-EP User Manual