4.3.3 Specifications
System data
Connection
Fieldbus protocol
Process image
Number of modules
Configuration interface
Transfer rate
Supply
Supply voltage for system and inputs
Supply voltage for outputs
Max. feed-in current for input modules
Max. feed-in current for output modules
Current consumption from system current path
I
SYS
Connection data
Type of connection
Conductor cross-section
General data
Operating temperature
Storage temperature
Air humidity (operation/transport)
Width
Depth
Height
Weight
Configuration
Parameter
IP address USB port
†
Process alarm
Diagnostic
Behavior of outputs on fieldbus error
Module behavior on hot swap
Data format
Webserver via Ethernet
Coupler control
†
Change requires restart of the network adapter.
GFK-2958E
Chapter 4 Detailed Descriptions of the Fieldbus Network Adapters
EPXETC001
Process data
Parameter data
Diagnostic data
Fieldbus
RTSi-EP system bus
Single-wired, fine-wired
ESI file is available on the Support website
for download and import into Programmer Tool which supports
EtherCAT. The ESI supporting a firmware release is part of the firmware
upgrade kit available on the Support website.
Overview of the Editable Parameters EPXETC001
Optional values
192.168.1.202; 192.168.2.202, 192.168.3.202,
192.168.4.202,
192.168.5.202
disabled / enabled
disabled / enabled
All outputs off / Enable substitute value/ Hold last
value
Continue data exchange / behavior like fieldbus error
Motorola / Intel
disabled / enabled / enabled
Reserved
RSTi-EP User Manual
2 x RJ-45
EtherCAT
max. 1024 bytes
max. 64*64 = 4 KB
max. 64*50 = 3200 bytes
max. 64 active
Micro USB 2.0
Max. 100 Mbps
Max. 48 Mbps
20.4V – 28.8V
20.4V – 28.8V
10 A
10 A
110 mA
Spring style
-20°C to +60°C (-4 °F to +140 °F)
-40°C to +85°C (-40 °F to +185 °F)
5% to 95%, noncondensing as per IEC 61131-2
52 mm (2.05 in)
76 mm (2.99 in)
120 mm (4.72 in)
227 g (8 oz)
0.14 – 1.5 mm
(AWG 26 – 16)
2
http://support.ge-ip.com
Default
192.168.1.202
disabled
disabled
All outputs off
Continue data
exchange
Motorola
disabled / enabled
Off
72